Temp High Alarm; Compress Type; Incremntl Energy - Honeywell Mini-AT User Manual

High performance, ptz electronic volume corrector
Table of Contents

Advertisement

Item
No.
Item Name
————————————————————————————————————————
146

TEMP HIGH ALARM

147

COMPRESS TYPE

Note: When selecting AGA-8, items 053 ,054 and 055 are disabled. However, the values at these items may
be changed for reference only. AGA8 software must be used to create a computer file (*.aga), which includes
user selectable values for Specific Gravity, %N
AT using "Transfer" | "Send AGA8 Factors" with Mini-AT Link Software. An AGA-8 file with defaulted
values for Specific Gravity = 0.6000, %N
Software package. Other values for Specific Gravity, %N2 and %CO2 will require AGA-8 software to create
a new .aga file(s).
148

INCREMNTL ENERGY

Mini-AT User Guide
Description
This item (146) indicates if a high temperature alarm was
generated. During a wake cycle, if the measurement for item 026
(GAS TEMPERATURE) is a value greater than the value entered
at item 028 (TEMP HILIM), an alarm is initiated and is indicated
by placing dots on the LCD and "11111111" at item 146.
"00000000" at item 146 indicates there is no Temperature
High Alarm. The alarm indicators will remain active until
manually cleared (by software) or automatically when RBX
(item 165) is enabled. Also see item 106. The Temperature
High Limit value (item 028) is user selectable and is normally set
somewhere between 50 and 100% of transducer range.
Default = 00000000
Selection to allow the user to choose the type of gas
compressibility calculation employed during each correction cycle
wake-up. Selection "0" (NX-19) results in the implementation of
AGA-3 / NX-19 Supercompressibility calculations. Selection "1"
(AGA-8) results in the implementation of AGA-8 calculations.
Select: 0 - NX-19---Default
1 - AGA-8
and %CO
. The file must be transferred to the connected Mini-
2
2
= 0.0000 and %CO
2
Same as item 140 (Energy) but is initialized to 00000000 after
every TIME log-trigger (item 202). If interrogated, the value
displayed indicates the most recently logged value.
Default = 00000000
= 0.0000 is provided with each Mini-AT Link
2
111