7.3 Function setting

• Function setting can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information. (Set
IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit on before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00
Standard
Filter
01
Longer
indicator
11
interval
02
Shorter
00
Enable
01
Disable
Filter
indicator
13
Display only
action
on central
02
remote
controller
00
Standard
Cool air
tem-
30
01
Adjust (1)
perature
trigger
02
Adjust (2)
00
Standard
Heat air
01
Adjust (1)
tem-
31
perature
02
Adjust (2)
trigger
03
Adjust (3)
00
Enable
Auto
40
restart
01
Disable
00
Super low
Cool Air
Follow the
Preven-
43
setting on
01
tion
the remote
controller
00
Start/Stop
Emergency
01
stop
External
46
control
02
Forced stop
00
All
Error re-
Display only
47
on central
port target
01
remote
controller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
off
01
Stop
Default
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger tempera-
ture. To lower the trigger tempera-
ture by 6 degrees C, use setting 01.
To lower the trigger temperature
by 4 degrees C, use setting 02. To
raise the trigger temperature, use
setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor
unit by this function in normal
operation.
Be sure to operate by the control
unit, converter or external input
device.
Restrain the cold airfl ow with making
the airfl ow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is off in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
Function
Function
Setting number
number
00
Mode 0
01
Mode 1
Switching
02
Mode 2
func-
tions for
03
Mode 3
external
60
04* Mode 4
inputs and
external
05
Mode 5
outputs
06* Mode 6
terminals
07
Mode 7
08
Mode 8
Auxiliary
00
heater
control 1
Auxiliary
01
heater
control 2
Heat pump
02
prohibition
Control
control
switching
61
Heater
of external
selection
heaters
03
control using
outdoor tem-
perature 1
Heater
selection
04
control using
outdoor tem-
perature 2
00
Setting 0
Operating
01
Setting 1
tem-
02
Setting 2
perature
62
switching
03
Setting 3
of external
heaters
04
Setting 4
05
Setting 5
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON = Room temperature - set temperature
00
01
00
t < -5.4°F (-3°C)
01
t < -3.6°F (-2°C)
02
t < -3.6°F (-2°C)
03
t < -5.4°F (-3°C)
04
t < -7.2°F (-4°C)
05
t < -9.0°F (-5°C)

8. TEST RUN

8.1 Test run using outdoor unit (PCB)

• Refer to the installation manual for the outdoor unit if the PCB for the outdoor unit is to be
used for the test run.

8.2 Test run using remote controller

• Refer to the installation manual for the remote controller to perform the test run using the
wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicators fl ash
slowly at the same time.
Default
Details
• Set this function when connecting
the VRF system to a ventilator,
economizer, humidifi er, or other
external device.
• The connection terminal functions
can be changed depending on the
type of external device. For details
of the connection terminal func-
tions, see the Design & Technical
Manual.
* When an electric heater is con-
nected to this unit, "04 (Mode 4)
and "06 (Mode 6)" cannot be used.
Do not set them.
Sets the control method for the exter-
nal heater being used. For details of
the control method, see the Design
& Technical Manual.
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions when
the external heater is ON". For a
more detailed explanation, see the
Design & Technical Manual
Set value of function: 61
02
03
t ≤ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≤ -3.6°F (-2°C)
t ≤ -5.4°F (-3°C)
t ≤ -7.2°F (-4°C)
t ≤ -9.0°F (-5°C)
04
En-14