Except as noted below, refer to the specifications provided in the HP
ProCurve Switch 4000M and 8000M Installation Guide.

NEBS Compliance

The HP DC ProCurve Switch has been tested by an independent
laboratory and found compliant with Telcordia (formerly Bellcore) NEBS
GR-63-CORE, Network Equipment-Building System (NEBS)
Requirements: Physical Protection; and GR-1089-CORE, Electromagnetic
Compatibility and Electrical Safety – Generic Criteria for Network
Telecommunications Equipment. NEBS compliance includes all "Level 3"
criteria plus all applicable "Other Criteria" of Telcordia SR-3580,
Network Equipment-Building System (NEBS) Criteria Levels.
The HP DC ProCurve Switch is suitable for connection to intrabuilding
or non-exposed wiring or cabling only. For compliance with NEBS
lightning transient requirements, only shielded interface cables (STP)
may be used and the cables must be grounded at both ends. For
non-NEBS installations, unshielded twisted-pair (UTP) cables may be
used.

Electrical

Nominal input voltage
Input current:
Input voltage range:
36
-48 or -60 V DC
8 A maximum, 4 A typical at -48 V DC
-36 to -72 V DC
Appendix A