Closing Spring Gag Interlock; Key Locks; Padlocks; Stationary Auxiliary Switch - GE POWER/VAC 4.16 Instructions Manual

Metal-clad switchgear for power-vac circuit breaker types vb-4.16, vb-7.2, vb-13.8, vb1-4.16, and vb1-13.8
Table of Contents

Advertisement

o
00
m
oo
1
Racking Nut
2
Bearing
3
Jack Screw
4
Rail
5
Disconnect
/
Test Slot
6
Operating CAM
7
Connect
Slot
op
U
.
Fig
.
43 Closing Spring Discharge
Interlock
CLOSING SPRING GAG INTERLOCK
An interlock is provided at either the front or
rear on the
left side of
the breaker
frame
to prevent
racking in a breaker
which has the spring
-
blocking device
(
pin or plate
)
in
the
gagged position
.
The spring
-
blocking device must be re
-
moved
so
that the
interlock interference may reset
to allow
the breaker to be racked
.
r
O
PH
O
OO
See breaker instruction book GEK 90207 or GEK 90208
for use of the closing spring blocking device
.
CAUTION : Gagging
closing springs when they
are in
the
discharged position
can
damage the breaker
.
The breaker
side frame may be deformed and
/
or
the gearmotor may be
damaged
.
Fig
.
44
Interference Interlock
The second position for padlocks (
5
)
is behind
the key
lock
.
A padlock in this slot will
prevent any
motion of the
racking mechanism by keeping the hexagon turning shaft
covered
.
KEY LOCKS
On the lefthand breaker racking mechanism
track is a
provision for a key lock
.
The purpose of this lock is to keep
the breaker from closing
in
the
" Test
" and
" Connect "
positions by operating the negative interlock
see
Fig
. 41 . To
remove the key ( 3 ) , push slide
(
1
) to the
rear and extend the
bolt
(
4
)
of the lock into slot
.
This allows
the key to be re
-
moved and prevents the breaker from closing
.
The key lock
does not prevent motion of the racking mechanism
.
STATIONARY AUXILIARY SWITCH
An auxiliary switch can be provided at the bottom of the
breaker compartment
so that additional
contacts
can
be
actuated by the operation of the breaker
.
The breaker will
operate this
switch
when
it is in
the "
Test
"
or "
Connect
"
position
.
See
Fig
.
45
.
BREAKER POSITION SWITCH
PADLOCKS
A position switch can be provided at the bottom of a
breaker compartment
so
that
it will be operated
by
a
bracket
on the breaker
frame when the
breaker
is in
the "
Connect
"
position
.
When the breaker
is withdrawn
,
a spring will re
-
turn the
switch
to
its normal position
.
See
Fig
.
45
.
Two positions for a possible 3
padlocks each
are
provided
on
the racking
mechanism
.
See Fig
. 42
.
The front position
keeps the breaker
from closing in
the " Test " and "
Connect
"
position . To obtain this position push slide
(
1
)
Fig
.
42 to the
rear
and insert the padlock
in the slotted opening just
forward of the keylock
(
3
)
.
This gives
the
same
interlocking
functions as
the keylock and does not block the motion of
the racking mechanism
.
SPACE HEATERS
Space heaters are provided in all outdoor equipment in
order to keep the
inside temperature several degrees higher
42