9.3
Diagnostic event in the operating tool
If a diagnostic event is present in the device, the status signal appears in the top left status
area of the operating tool along with the corresponding symbol for the event level in
accordance with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
‣
Navigate to the Diagnostics menu
In the Actual diagnostics parameter the diagnostic event is shown with event text
9.4
List of diagnostic events
Diagnostic
Short text
number
Diagnostic of electronic
270
Main electronic
failure
271
Main electronic
failure
272
Main electronic
failure
283
Memory content
Diagnostic of configuration
410
Data transfer
411
Up-/download active
435
Linearization
438
Dataset
441
Current output 1
491
Current output 1
simulation
585
Simulation distance
586
Record map
Diagnostic of process
801
Energy too low
825
Operating
temperature
Diagnostics and troubleshooting
Remedy instructions
Exchange device
1. Restart device
2. If failure remains, exchange
device.
1. Restart device
2. Check enviroment for strong
EMC fields
3. If failure remains, exchange
device.
1. Transfer data or reset device
2. Contact service
1. Check connection
2. Retry data transfer
Up-/download active, please wait
Check linearization table
1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
1. Check process
2. Check current output settings
Deactivate simulation
Deactivate simulation
Recording of mapping
please wait
Increase supply voltage
1. Check ambient temperature
2. Check process temperature
Status signal
Diagnostic
[from the
behavior
factory]
[from the
factory]
F
Alarm
F
Alarm
F
Alarm
F
Alarm
F
Alarm
C
Warning
F
Alarm
M
Warning
S
Warning
C
Warning
C
Warning
C
Warning
S
Warning
S
Warning