IDR-2P, -2A & -6A Repeaters User Manual
4.4.2 LEDs/LCD/Buzzer Test (ID50 -2A/

4.4.3 Pushbutton Test (ID50 -2A)

4.4.4 Log (ID50 -2A/-2P)

25
-2P)
Note: This test is available for the -2P at access
level 1; the -2A requires access level 2.
All pixels on the LCD are switched on and then
off, the buzzer sounds intermittently, and the
LEDs light sequentially in a continuous pattern
from bottom right to top left.
At access level 2 only: To change the contrast
of the LCD, press the
repeatedly to give the best display, then press
to return to the display prior to test.
If no change is made to the contrast, the test
stops automatically and the LCD returns to the
display prior to test.
Press each pushbutton in turn. Verify that:
a. The buzzer beeps.
b. The LCD displays the name of the
pushbutton (does not for pushbuttons that
are not used).
Turn the keyswitch to access level 1 to exit
the test.
Use the
and
arrows to scroll through
the log messages. Press
System Normal display.
Note: This option is available for the -2P at
access level 1; the -2A requires access
level 2.