Download Print this page

Aiphone NDR-10RS Instructions

Ndr lamp memory master station with external control capability for rescue assitance

Advertisement

Quick Links

NDR Lamp Memory Master Station with External Control Capability for Rescue Assitance
NDR-10RS NDR-20RS NDR-30RS NDR-40RS
NDR-10ARS NDR-20ARS NDR-30ARS NDR-40ARS
The NDR-nRS Lamp Memory System is designed for use with the NE-NVP-RA Rescue Assistance sub stations.
The NE-NVP-RA provides communication and call status indication for applications with ADA requirements for
Areas of Rescue Assistance. The NE-NVP-RA features Braille signage, a large red call button, and "call placed"
and "help coming" LED indicators. The sub station flush mounts into a 3-gang masonry-type box, or surface
mounts in the SBX-NVP. Tamper proof screws are provided, along with a wrench for installation. Remote lamps
can be added for better visibility of a station's status. The NDR-nRS master station is equipped with a door
release button and a reset button to reset calls at the master station. The NDR-nRS has outputs to activate an
external device, such as a CCTV camera when the associated sub station is selected, or selectively controlling
the corresponding door strike or maglock.
WIRING DIAGRAM:
NDR-20RS
1
2
3
~
20
E
S
H
External
Terminal Block
1
2
3
~
20
PS-2410A
+
+
-
-
Individual Components for System:
NDR-nRS
Master station with selective contact output capability (10, 20, 30, 40)
NDR-nARS Master station w/hndst andcontact output capability (10, 20, 30, 40)
ND-20AS
20-call Add-on Selector with selective output capability (Require PS-2410A)
ND-40AS
40-call Add-on Selector with selective output capability (Requires PS-24E)
RY-PA
Relay for selective output (1 per station requiring external contact)
PS-2410A24V DC, 1A Power Supply for 10-20 station systems
PS-24E
24V DC, 2A Power Supply for 30-40 station systems
Vandal proof sub station with call status indicators and braille signage
NE-NVP-RA
IMPORTANT:
1. RY-PA must be used for each additional contact
to isolate AC voltage from the intercom circuit.
2. Extra contact connections and L are on separate
terminal block. NDR-30/40RS have two terminal blocks.
NDR-RS
- INSTRUCTIONS -
SYSTEM USED FOR CCTV CAMERA CALL-UP
NE-NVP-RA
Red
Green
jumper
Blu
Pur
Blk
Yel
Org
BLK
RY-PA
YEL
BLK
#1
L
Equipment for each station that requires
both a constant closure and momentary
closure when a channel is selected:
2 RY-PA relays
1 Diode (1N4001)
NE-NVP-RA
Red
Green
jumper
Blu
Pur
Blk
Yel
Org
RY-PA
BLK
YEL
#3
RY-PA
YEL
Closure for Station #2
#2
Normally Open contacts remain
Closure for Station #3
closed as long as master has sub
station selected.
Terminal Block
1
L
2
NDR-RS Master
H
NDR-RS TERMINAL DEFINITIONS:
+
-
1~40
E
S
H
NE-NVP-RA
Red
Leave green
Green
jumper
jumper intact
Blu
Pur
Blk
Yel
Org
Closure for Station #1
DUAL FUNCTIONS FROM EACH CHANNEL:
RY-PA
BLK
YEL
#1
RY-PA
YEL
BLK
#2
RY-PA
BLK
RY-PA
BLK
Positive 24V DC
Negative
Station number
Common communication
Sends "call placed" tone to sub
Resets call signals at sub when RESET
button is pressed.
Special
Order
Products
Momentary closure #1
Constant closure #1
Momentary
YEL
#1
closure #2
Constant
YEL
#2
closure #2
Pg. 1

Advertisement

loading

Summary of Contents for Aiphone NDR-10RS

  • Page 1 NDR Lamp Memory Master Station with External Control Capability for Rescue Assitance NDR-10RS NDR-20RS NDR-30RS NDR-40RS NDR-10ARS NDR-20ARS NDR-30ARS NDR-40ARS The NDR-nRS Lamp Memory System is designed for use with the NE-NVP-RA Rescue Assistance sub stations. The NE-NVP-RA provides communication and call status indication for applications with ADA requirements for Areas of Rescue Assistance.
  • Page 2 2 conductors homerun to sub station, or loop multi-conductor with 1 common + 1 individual wire per sub station on wire run. Separate 2 conductor from RY-PA to external device. Shielded cable is recommended. Use Aiphone #822202 (22AWG) or #821802 (18AWG) wire (2 cond.). Wiring Distance: 420' with 22AWG;...

This manual is also suitable for:

Ndr-20rsNdr-30rsNdr-40rsNdr-10arsNdr-20arsNdr-30ars ... Show all