Interlock Position Indicator; Test Position; Operating Position; Interlock - Siemens DHR Series Installation, Operation & Maintenance Instructions Manual

Vacuum circuit breakers 4.16kv to 15kv
Table of Contents

Advertisement

Vehicle Description
the test position. The rollers on the arms strike vertical
angles on the cell wall and stop the breaker at the test
position. If the breaker is to be operated at this position,
remove the crank and engage the secondary contacts in
the manner described in the section under Secondary Con-
tacts. To move the breaker from the test position to the
fully engaged operating position, put the crank on the shaft,
push in and rotate to engage the levering-in coupling, and
crank clockwise. The torque required will increase when
the primary contact fingers engage the stationary contact
studs in the cell. Continue cranking to the end of the travel
where the interlock will again fall free, pushing the crank
back out. Remove the crank. The indicator on the panel
will again point to the word "OPERATE".
To remove the breaker from the operating position, first
check that the breaker is open. The levering-in device can-
not be engaged unless the breaker contacts are open. Put
the crank on the operating shaft, push in and rotate to en-
gage the coupling, and turn counterclockwise until the
breaker returns to the test position. Remove the crank.
The breaker may now be operated at the test position or
rolled out of the cell.

Interlock Position Indicator

The interlock position indicator (Figure 2) gives a positive
indication of the position of the breaker interlock. It oper-
ates from the levering-in device shaft. When the indica-
tor points to the word OPERATE, the interlock is free and
the breaker may be closed or tripped. When the indicator
points to the word INTERLOCKED, the interlock is func-
tioning and the breaker cannot be closed. Since the inter-
lock is operative only when the breaker is in fan interme-
diate position between fully engaged and fully withdrawn,
it also serves as a means of indicating that the breaker is
in the Operating Position and the main disconnecting con-
tacts fully engaged, or that it is in the Test Position with
the contacts separated.
Figure 2. Interlock Position Indicator

Test Position

The breaker may be rolled into the metal clad cell until the
rollers on the levering-in device stop against a pair of ver-
tical angles welded into the cell. The levering-in device is
not operated. This is the test position in which the breaker
primary contacts are separated from the energized con-
tacts in the cell, and a metal shutter is closed completely
isolating all high voltage parts from the breaker. The sec-
ondary contacts may be engaged and the breaker oper-
ated safely for test purposes without the arc chutes or bar-
rier.

Operating Position

The breaker may be moved from the test to the operating
position by engaging the levering-in device and rotating
the levering-in crank clockwise. As the breaker travels
beyond the Test Position, the metal shutter covering the
high voltage primary contacts will be automatically opened
by the shutter rollers which are locate on each side of the
breaker frame at the rear (Figure 1a). At the end of the
travel, all the breaker contacts are engaged. This is the
Operating Position.

Interlock

The interlock on the DH breakers has two functions to per-
form. First, it prevents the breaker from being moved from
the test to the operate position or vice versa with the con-
tacts closed. Second, if the breaker is in some intermedi-
ate position between the test and operate positions, it pre-
vents the contacts from being closed.
This interlocking action is accomplished by having a rod,
operated by the breaker mechanism, and a pin operated
by the levering-in device, move at right angles to each
other.