Page 1
CURENT REVISION DATE: 4/20 DRAWING CHANGE ECN# DATE PUBLISHER FILE CREATED; REFRESHED LAYOUT DESIGN B002026 4/29/20 THIS DRAWING IS THE EXCLUSIVE AND CONFIDENTIAL PROPERTY OF AMEREX CORPORATION. IT SHALL NOT BE DUPLICATED, USED OR DISCLOSED TO OTHERS PN 14425 04/2020...
Page 2
There are substitute parts available, which are incorrectly labeled as U/L component parts, some are advertised as Amerex type. None of these meet U/L requirements, and all of them void the Amerex extinguisher warranty and U/L listing. DO NOT SUBSTITUTE.
Page 3
INTRODUCTION This manual covers specific instructions for the Amerex Halotron I hand-portable extinguishers. Special maintenance and recharge instructions contained in this manual apply to these extinguishers only. Halotron I “Clean Agent” extinguishers are designed for Class-A,-B, and -C hazards formerly protected with Halon 1211 extinguishers.
Page 4
CINDER BLOCK OR CEMENT: Mount wall hanger bracket using one ¼-inch toggle bolt or masonry lead screw expansion anchor through center hole in wall bracket. CONCRETE OR TILE WALLS: Mount wall-hanger bracket using one ¼-inch masonry lead screw expansion anchor through center hole in wall bracket. FOR TILE WALLS: locate in joint. STEEL POSTS OR BEAMS: Special tools and fasteners are required –...
Page 5
2. Inspect the extinguisher for damaged, missing, or substitute parts. Only factory replacement parts are approved for use on Amerex fire extinguishers. 3. Weigh extinguisher and compare with weight printed in the Maintenance section on the nameplate.
Page 6
5. Inspect the interior of the cylinder following CGA Visual Inspection Standard, C-6. 6. Install the valve assembly to the cylinder in a clockwise direction. Install the proper Amerex recharge adapter and draw a vacuum of 27" of mercury (adjusted for altitude variations – see your vacuum pump manual for detailed instructions).
Page 7
DEPRESSURIZED. THE EXTINGUISHER MUST BE COMPLETELY DEPRESSURIZED BEFORE ANY ATTEMPT IS MADE TO REMOVE THE VALVE ASSEMBLY AND CORRECT THE LEAKAGE PROBLEM. SEE INSTRUCTIONS PACKAGE WITH THE AMEREX HALOTRON I RECHARGE KIT PN 14538 OR GETZ HALOTRON RECOVERY SYSTEM FOR THE PROPER METHOD OF DEPRESSURIZING THE EXTINGUISHER TO AVOID UNNECESSARY DISCHARGE AND MINIMUM AGENT LOSS.