▶ Ensure that all pre-fail/fail status issues have been resolved in ServerView
Operations Manager.
Using Infrastructure Manager
The status of server (node) which failed memory module is installed becomes
error.
When replacing the memory module, the status will be updated after getting
information manually or automatically updated daily.
Proceed as follows to get node information with Infrastructure Manager:
▶ Start up the GUI of the Infrastructure Manager and login.
▶ Display the node list from menu (manage > node).
▶ Select the target node and display the detail screen.
▶ Execute getting node information from action menu.
5.3.6.3

Locating the defective server

Use the ID indicator for easy identification of the server, especially when
working in a datacenter environment or a server room:
▶ Press the ID button on the front panel, use the iRMC S5 web interface or the
ServerView Operations Manager user interface to switch on the system
identification LEDs.
For more information, see the "ServerView Suite Local Service
Concept (LSC)" manual and the iRMC user guides.
▶ When using ServerView Operations Manager to toggle the ID indicator,
choose Single System View and press the Locate button.
▶ Remember to switch off the ID indicator after the maintenance task has
been concluded successfully.
RX4770 M6
Upgrade and Maintenance Manual
Basic software procedures