3.6.4 Mounting direction

(1) For the following models, pay attention to attaching position as overcurrent tripping is of fHydraulic-
magnetic type and the tripping characteristic varies depending on mounting position. It is recom-
mendable to use them attached vertically.
Moulded-case circuit
breaker
Earth leakage circuit
breaker
Moulded-case circuit breaker
for motor protection
Circuit protector
100%
107%
ON
ON
ON
ON
110%
ON
ON
ON
ON
107%
100%
Rate of change of rated
current by mounting angle
(For NF, NV, MB)
(2) Thermal-magnetic type and electronic type are not affected by mounting direction.