Inspection At Arrival; Conditions During Transport And Storage; Transport; Storage - Mitsubishi Electric C Series Handling And Maintenance

Moulded case circuit breakers, earth leakage circuit breakers, earth leakage relays & circuit protectors
Table of Contents

Advertisement

3.4 Inspection at arrival

(1) Make sure that the packing case is free from any abnormality such as breaking and wetting.
(2) Referring to the name plate, make sure that the delivered breaker is in conformity with your order.
(3) Check for the parts contained in the same package.
1 Mounting screws
2 Terminal screws
3 Insulation barriers (The barrier is contained in the same package for some models, but not for other
models.)
4 Terminal covers (The cover is contained in the same package for some models, but not for others.)
Note: At unpacking, be careful so that the sealing pags may not be scattered around.

3.5 Conditions during transport and storage

3.5.1 Transport

Packing and transportation shall be
carried out with care
Never drop the packing.

3.5.2 Storage

Storage temperature
40°C
Keep within
this range.
–20°C
Average temperature for 24 hours,
however, shall not be higher than 35°C.
Place of low dust content
19
Don't bring the breaker by holding the
flash plate for carrying.
Carrying in this manner is dangerous
as the breaker may drop.
Avoid humid air.
Relative humidity: 85% max.
• Don't leave the breaker in a humid
place for a long time.
• Keep the breaker so as not be dewed.
Housed in a packing case for storage
Don't bring the breaker up with
holding the wires for carrying.
Holding on the attached lead wires of internal
accessories for carrying as unreasonable force
is applied to the attached wires.
Avoid corrosive gas.
Ammonia
H
S
2
Storage the breaker in the environment
of no corrosive gas.
H
S 0.01 ppm max. SO
0.05 ppm max.
2
2
NH
0.25 ppm max.
3
Avoid direct sunlight.
Avoid direct insolation during storage.