Download Print this page

Technical Data - Siemens OpenAir GEB 1 Series Technical Basics

Actuators without spring return
Hide thumbs

Advertisement

AC 24 V supply
(SELV/PELV)
for GEB13..1, GEB16..1..
AC 230 V power supply
for GEB33..1
Function data
Inputs
Positioning signal for GEB13..1
Positioning signal for GEB33..1
Positioning signal
for GEB16..1..
Adjustable characteristic function
for GEB163.1, 164.1
Outputs
Position indicator
for GEB16...1
34/44
Siemens
Building Technologies
8

Technical data

Operating voltage
Frequency
Safety extra-low voltage (SELV) or
Protection by extra-low voltage (PELV) as per
Requirements for external safety insulating transformer (100 % duty)
Supply line fuse
Power consumption GEB13..1: Running
GEB16..1: Running
GEB161.1E/MO: Running
Operating voltage
Frequency
Supply line fuse
Power consumption:
Nominal torque
Maximum torque (blocked)
Minimum holding torque
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
Runtime for 90° rotary angle
Mechanical life
Operating voltage AC 24 V
Operating voltage AC 230 V (wires 4-6)
Input voltage (wires 8-2)
Current consumption
Input resistance
Max. permissible input voltage
Protected against faulty wiring
Neutral zone for non-adjustable characteristic function
for adjustable characteristic function
Hysteresis
for non-adjustable characteristic function
for adjustable characteristic function
Communication
Modbus RTU
Number of nodes
Address range
Transmission formats
Baudrates (kBaud)
Termination
Adjustable with 2 potentiometers:
Offset Uo
Span ΧU
Max. input voltage
Protected against faulty wiring
Output signal (wires 9-2)
Output voltage U
Max. output current
Protected against faulty wiring
Actuators without spring return GEB...1
Holding
Running
(wires 1-6)
(wires 1-7)
(wires 4-7)
AC 24 V ° 20 % (SELV) or
AC 24 V class 2 (US)
50/60 Hz
HD 384
as per EN 61 558
max. 10 A
3.5 VA / 3.5 W
5.5 VA / 5.5 W
6 VA / 5.5 W
1.5 W
AC 230 V ° 10 %
50/60 Hz
max. 10 A
3 VA / 3 W
15 Nm
30 Nm
15 Nm
90 °
95° ± 2°
150 s
5
10
cycles
clockwise
counterclockwise
clockwise
counterclockwise
DC 0...10 V / 2...10 V
0.1 mA
> 100 kς
DC 35 V
max. AC 24 V
200 mV
2 % of ΧU
70 mV
0.7 % of ΧU
RS-485, not galvanically separated
Max. 32
1...247 / 255
Default: 255
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Default: 1-8-E-1
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 /
115.2
Default: Auto
120 Ω el. Switchable
Default: Off
DC 0...5 V
DC 2...30 V
DC 35 V
max. AC 24 V
DC 0...10 V
DC ° 1 mA
max. AC 24 V
CM2Z4621en
2017-05-26