Roger MC16-PAC-3-KIT Installation Manual
Hide thumbs Also See for MC16-PAC-3-KIT:

Advertisement

MC16-PAC-4-KIT Installation Manual
MC16-PAC-3-KIT and MC16-PAC-4-KIT Installation Manual
This document contains minimum information that is necessary for initial setup
and installation of the kit. The detailed description of configuration parameters
and functionalities of all components is specified in respective Operating
manuals available at www.roger.pl.
I
NTRODUCTION
MC16-PAC-3-KIT is designed to control three doors while MC16-PAC-4-KIT is
designed to control four doors in RACS 5 system. All doors can be read-in or
read-in/out type when equipped with MCT series readers (RS485). The kit
includes respectively MC16-PAC-3 or MC16-PAC-4 access controller, MCX4D
expander and ME16 metal box with PS4D power supply unit. The box is adapted
to installation of 17Ah battery for emergency supply. All elements of controlled
door including readers and door locks can be supplied from the kit.
C
R
ONFIGURATION WITH
OGER
Low level configuration with RogerVDM software enables to define basic
parameters of devices and it mainly concerns MC16 controller. Additionally in
case of MCT series readers it is necessary to define their individual addresses
according to their installation manuals.
MC16 programming procedure with RogerVDM software:
1. Connect the controller to Ethernet network and define the IP address of your
computer in the same subnetwork as the controller with 192.168.0.213
default IP address.
2. Start RogerVDM program, select MC16 v1.x device, the latest firmware
version and Ethernet communication channel.
3. Select from the list or enter manually the IP address of controller, enter 1234
communication key and start the connection with the controller.
4. In the top menu select Tools and then Set communication key to define your
own password for the controller.
5. In the main window specify your own IP address of the controller.
6. Optionally enter comments for controller and its object to facilitate their
identification during further configuration of the system.
7. Optionally backup settings clicking Send to File...
8. Click Send to Device to update the configuration of controller and disconnect
by selection of Device in the top menu and then Disconnect.
C
VISO
ONFIGURATION WITH
High level configuration with VISO software enables to define the logic of
controller. More information is given in MC16 Operating manual and AN006
application note.
M
EMORY RESET
Memory reset procedure resets all settings to default ones and results in
192.168.0.213 IP address and empty communication key.
MC16 memory reset procedure:
1. Disconnect power supply
2. Short CLK and IN4 lines.
3. Restore power supply, all LEDs will flash and wait min. 6s.
4. Remove connection between CLK and IN4 lines, LEDs will stop pulsating and
LED2 will be on.
5. Wait approx. 1.5 min till LED5+LED6+LED7+LED8 are pulsating.
6. Restart the controller (switch power supply off and on)
7. Start RogerVDM and make low level configuration.
F
IRMWARE UPDATE
New firmware can be uploaded to the controller with RogerVDM software. The
latest firmware file is available at www.roger.pl.
MC16 firmware update procedure:
1. Connect with the controller using RogerVDM software.
2. Backup settings by clicking Send to File...
3. In the top menu select Tools and then Update firmware.
4. Select firmware file and then click Update.
5. After firmware update wait till LED8 is pulsating.
6. Make or restore low level configuration in RogerVDM software.
Note: During the firmware update process, it is necessary to ensure continuous
and stable power supply for the device. If interrupted, the device may require
repair by Roger.
Roger Access Control System
Controller Firmware version: 1.6.2 or newer
Document version: Rev. C
VDM
PROGRAM
PROGRAM
Product version: 2.0
P
OWER SUPPLY
The kit is supplied from PS4D power supply unit. The metal box offers space for
installation of typical 17Ah backup battery which is connected to BAT+ and BAT-
terminals of MCX4D expander.
Fig. 1 MC16-PAC-3-KIT or MC16-PAC-4-KIT
The installation can be done only by qualified person with all
necessary certificates concerning connection and maintenance
of 230VAC and low voltage networks.
Prior to starting the installation it is necessary to ensure that
230 VAC circuit is disconnected. All works inside the box must
be carried out with 230VAC supply voltage disconnected.
It is forbidden to use the kit without properly executed and
operational earthing system.
T
AMPER DETECTOR
The metal box is equipped with door contact which can be connected to one of
the inputs (e.g. IN8) and GND terminal of the controller. The anti-sabotage
function can be assigned to the input within high level configuration of the
system.
A
PPENDIX
Table 1. MC16 screw terminals
Name
BAT+, BAT-
AC, AC
AUX-, AUX+
TML-, TML+
IN1-IN8
GND
OUT1-OUT6
A1,B1
CLK, DTA
A2,B2
NO1, COM1, NC1
NO2, COM2, NC2
Table 2. MCX4D screw terminals
Name
BAT+, BAT-
VIN+, VIN-
AUX+, AUX-
VOUT+, VOUT-
Description
Not used in kit
Not used in kit
12VDC input power supply
Not used in kit
Input lines
Ground
15VDC/150mA transistor output lines
RS485 bus
Not used in kit
Not used
30V/1.5A DC/AC (REL1) relay
30V/1.5A DC/AC (REL2) relay
Description
Backup battery
13.8VDC input power supply
13.8VDC/0.2A
output power supply (for general
purpose)
13.8VDC/0.2A output power supply (for controller)
2020-03-06
1/2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MC16-PAC-3-KIT and is the answer not in the manual?

Questions and answers

Summary of Contents for Roger MC16-PAC-3-KIT

  • Page 1 MCX4D expander. NTRODUCTION MC16-PAC-3-KIT is designed to control three doors while MC16-PAC-4-KIT is designed to control four doors in RACS 5 system. All doors can be read-in or read-in/out type when equipped with MCT series readers (RS485). The kit includes respectively MC16-PAC-3 or MC16-PAC-4 access controller, MCX4D expander and ME16 metal box with PS4D power supply unit.
  • Page 2  In case of 17Ah backup battery it is recommended to configure 600mA battery charging current by means of jumper on MCX4D board. Contact: Roger Sp. z o. o. sp. k. 82-400 Sztum Gościszewo 59 Tel.: +48 55 272 0132 Fax: +48 55 272 0133 Tech.

This manual is also suitable for:

Mc16-pac-4-kit

Table of Contents