Troubleshooting - Honeywell D06F Installation Instructions Manual

Pressure reducing valve
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
9.4 Cleaning
Caution !
Do not use any cleaning agents containing solvents
and/or alcohol to clean the plastic parts!
Cleaning agents can lead to water damage!
If necessary, the filter bowl and the filter can be cleaned.
To be carried out by an installation company or the
operator.
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
o Use double ring wrench ZR06K
5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter cup hand-tight (without tools)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet

11. Troubleshooting

Problem
Beating sounds
Water is escaping from the spring
bonnet
Too little or no water pressure
The outlet pressure set does not
remain constant
Honeywell GmbH
GB
10. Disposal
The pressure reducing valve comprises:
• Stainless steel
• Steel
• Plastic
Cause
Pressure reducing valve is too
large
Diaphragm in valve insert is faulty
Shutoff valves up- or downstream of the
pressure reducing valve are not fully open
Pressure reducing valve is not set to the
desired outlet pressure
Filter in pressure reducing valve is conta-
minated
Pressure reducing valve is not fitted in flow
direction
Filter in pressure reducing valve is conta-
minated or worn
Valve insert, sealing ring or edge of nozzle
is contaminated or worn
Rising pressure on outlet (e.g. in boiler)
8
Observe the local requirements regarding correct
waste recycling/disposal!
Remedy
Call our Technical Customer Services
Replace valve insert
Open the shutoff valves fully
Set outlet pressure
Clean or replace filter
Fit pressure reducing valve in flow direction
(note direction of arrow on housing)
Clean or replace filter
Replace valve insert
Check check valve, safety group etc.
MU1H-1002GE23 R0108

Advertisement

Table of Contents
loading

This manual is also suitable for:

D06fhD06fnD06f-1/4zaD06fi

Table of Contents