Figure 9: Mts 4 Cabinet Dimensions - Motorola MTS LiTE Installation, Configuration And Basic Service Manual

For dimetra x core, dimetra express, dimetra ip scalable (dips), dimetra ip compact (dipc)/scalable.
Table of Contents

Advertisement

Figure 9: MTS 4 Cabinet Dimensions

The equipment cabinet may be installed against adjacent equipment, however the following minimal
distances must be retained:
25 mm on both sides of the cabinet
800 mm of free space in front of the cabinet
The cabinet front door has hinges on both sides and it can be opened right, left, or removed.
Suggested MTS 4 Site Layout on page 68
Additional free space is recommended at the front of the cabinet to allow service personnel easy
access to the equipment.
CAUTION: To enable service access and assure the passive cooling ventilation, the free space
above the cabinet must be at least 20 cm. The antenna cabling may require additional space.
NOTICE: Enable the opening of all doors to the equipment room to at least 90 degree. The
cabinet has a removable door.
shows the cabinet layout within a suggested site.