Installation Options with Racks and Cabinets

Installation Options with Racks and Cabinets
You can install the switch in the following types of racks using the rack-mount kit shipped with the switch:
• Open EIA rack
• Perforated EIA cabinet
The rack or cabinet that you use must meet the requirements listed in
Racks
The rack-mount kit enables you to install the switch into racks of varying depths. You can use the rack-mount
kit parts to position the switch with easy access to either the port connections end of the chassis or the end of
the chassis with the fan and power supply modules. For instructions on how to install the rack-mount kit, see
the
Installing the Switch, on page

Airflow Considerations

The switch comes with fan and power supply modules that have either port-side intake or port-side exhaust
airflow for cooling the switch. If you are positioning the port end of the switch in a cold aisle, make sure that
the switch has port-side intake modules with burgundy colorings on the fan and AC power supplies and green
markings on DC power supplies. If you are positioning the fan and power supply modules in a cold aisle,
make sure that the switch has port-side exhaust modules with blue colorings.

Installation Guidelines

When installing the switch, follow these guidelines:
• Record equipment and installation information in the forms presented in
• Ensure that there is adequate space around the switch to allow for servicing the switch and for adequate
• Ensure that you are positioning the switch in a rack so that it takes in cold air from the cold aisle and
• Ensure that the chassis can be adequately grounded. If the switch is not mounted in a grounded rack,
• Ensure that the site power meets the power requirements listed in
Cisco Nexus 9372TX ACI-Mode Switch Hardware Installation Guide
2
and Maintenance Records"
as you install and configure the switch.
airflow (see
exhausts air to the hot aisle. If there is blue coloring on the fan tray and AC power supply modules, the
switch is configured for port-side exhaust and you must position the fan and power supply modules in
a cold aisle. If there is burgundy coloring on the fan and AC power supply modules or green coloring
on the DC power supply modules, the switch is configured for port-side intake and you must position
the ports in a cold aisle.
we recommend connecting both the system ground on the chassis directly to an earth ground.
If available, you can use an uninterruptible power supply (UPS) to protect against power failures.
4.
Installing the Switch Chassis
General Requirements for Cabinets and
Appendix E, "Site Planning
Appendix B System
Specifications.