Electrical Data Dm150 (12-1/2 Ton) Std Efficiency W/O Pwrd Convenience Outlet; Electrical Data Dm150 (12-1/2 Ton) Std Efficiency W/Pwrd Convenience Outlet; Electric Heat Multipliers; Performance - York PREDATOR DM 078 Technical Manual

Standard efficiency single package air conditioners and single package gas/electric units 6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 nominal tons 9.0 eer
Table of Contents

Advertisement

246645-YTG-C-0708
TABLE 18: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
OD Fan
Compressors
Motors
Voltage
RLA
LRA
FLA
ea.
ea.
ea.
20.0
146.0
3.5
208
20.0
146.0
3.5
230
8.4
73.0
1.6
460
6.7
60.0
1.3
575
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 19: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/PWRD CONVENIENCE OUTLET
OD Fan
Compressors
Motors
Voltage
RLA
LRA
FLA
ea.
ea.
ea.
20.0
146.0
3.5
208
20.0
146.0
3.5
230
8.4
73.0
1.6
460
6.7
60.0
1.3
575
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 20: ELECTRIC HEAT MULTIPLIERS
VOLTAGE
NOMINAL
240
480
600
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
22
Supply
Pwr
Pwr
Blower
Exh
Conv
Motor FLA
Motor
Outlet
3
5
FLA
FLA
HP
HP
10.9
16.1
5.5
0.0
10.9
16.1
5.5
0.0
5.3
8.1
2.2
0.0
4.1
6.0
1.8
0.0
Supply
Pwr
Pwr
Blower
Exh
Conv
Motor FLA
Motor
Outlet
3
5
FLA
FLA
HP
HP
10.9
16.1
5.5
10.0
10.9
16.1
5.5
10.0
5.3
8.1
2.2
5.0
4.1
6.0
1.8
4.0
kW Cap. Multiplier
RATING
208
0.75
230
0.92
460
0.92
575
0.92
Electric Heater
Actual
Heater
Model No.
KW
Amps
None
--
--
2TP04521825
13.5
37.5
2TP04522425
18
50.0
2TP04523625
25.5
70.8
2TP04525425
40.6
112.7 154.5 161.0 161.4 167.9 175 175 175 175
None
--
--
2TP04521825
18
43.3
2TP04522425
24
57.7
2TP04523625
34
81.8
2TP04525425
54
129.9 143.5 150.0 150.4 156.9 175 175 175 175
None
--
--
2TP04521846
18
22.6
2TP04522446
24
30.1
2TP04523646
34
42.7
2TP04525446
54
67.8
None
--
--
2TP04521858
18
18.1
2TP04522458
24
24.1
2TP04523658
34
34.1
2TP04525458
54
54.2
Electric Heater
Actual
Heater
Model No.
KW
Amps
None
--
--
2TP04521825
13.5
37.5
2TP04522425
18
50.0
2TP04523625
25.5
70.8
2TP04525425
40.6
112.7
None
--
--
2TP04521825
18
43.3
2TP04522425
24
57.7
2TP04523625
34
81.8
2TP04525425
129.9
54
None
--
--
2TP04521846
18
22.6
2TP04522446
24
30.1
2TP04523646
34
42.7
2TP04525446
54
67.8
None
--
--
2TP04521858
18
18.1
2TP04522458
24
24.1
2TP04523658
34
34.1
2TP04525458
54
54.2
NOTES FOR TABLE 21 THROUGH TABLE 30:
Blower performance includes dry coil and 2" throwaway
filters.
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure
of the blower.
MCA
Max
Min. Circuit
w/Power
Fuse*
Ampacity
Exhaust
Size
(Amps)
(Amps)
(Amps)
3
5
3
5
3
HP
HP
HP
HP
HP HP HP HP
62.9
68.1
68.4
73.6
80
62.9
68.1
68.4
73.8
80
76.1
82.6
83.0
89.5
80
102.1 108.6 109.0 115.5 110 110 110 125
62.9
68.1
68.4
73.6
80
67.8
74.3
74.6
81.1
80
85.8
92.3
92.7
99.2
90 100 100 100
115.9 122.4 122.7 129.2 125 125 125 150
27.4
30.2
29.6
32.4
35
33.7
37.2
36.4
39.9
35
42.7
46.2
45.5
49
45
57.7
61.2
60.5
64
60
71.6
75.1
74.3
77.8
80
21.8
23.7
23.6
25.5
25
26.8
29.2
29
31.4
30
34
36.4
36.2
38.6
35
46
48.4
48.3
50.6
50
57.1
59.5
59.3
61.7
70
MCA
Max
Min. Circuit
w/Power
Fuse*
Ampacity
Exhaust
Size
(Amps)
(Amps)
(Amps)
3
5
3
5
3
HP
HP
HP
HP
HP HP HP HP
72.9
78.1
78.4
83.6
90
73.0
79.5
79.8
86.3
90
88.6
95.1
95.5 102.0 90 100 100 110
114.6 121.1 121.5 128.0 125 125 125 150
167.0 173.5 173.9 180.4 175 175 175 200
72.9
78.1
78.4
83.6
90
80.3
86.8
87.1
93.6
90
98.3 104.8 105.2 111.7 100 110 110 125
128.4 134.9 135.2 141.7 150 150 150 150
156.0 162.5 162.9 169.4 175 175 175 175
32.4
35.2
34.6
37.4
40
39.9
43.4
42.7
46.2
40
49
52.5
51.7
55.2
50
64
67.5
66.7
70.2
70
77.8
81.3
80.6
84.1
90
25.8
27.7
27.6
29.5
30
31.8
34.2
34
36.4
35
39
41.4
41.2
43.6
40
51
53.4
53.3
55.6
60
62.1
64.5
64.3
66.7
70
Johnson Controls Unitary Products
Max
Fuse
Size
w/Power
5
3
5
80
80
90
80
80
90
90
90
90
80
80
90
80
80
90
35
35
40
40
40
40
50
50
50
70
70
70
90
80
90
30
30
30
30
30
35
40
40
40
50
50
60
70
70
70
Max
Fuse
Size
w/Power
5
3
5
90
90 100
90
90 100
90
90 100
90
90 100
40
40
45
45
45
50
60
60
60
70
70
80
90
90
90
30
30
35
35
35
40
45
45
45
60
60
60
70
70
70

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Predator dm 090Predator dm 102Predator dm 120Predator dm 150Predator dm 078

Table of Contents