Blower Performance; Ton Standard Motor Down Shot Blower Performance - York PREDATOR DM090 Installation Manual

Single package air conditioners and single package electric units 7-1/2 to 12-1/2 ton (380v, 3 phase, 60 hz)
Hide thumbs Also See for PREDATOR DM090:
Table of Contents

Advertisement

TABLE 19: 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
0
ESP
††
CFM
BHP
W
0.2
-
-
-
0.4
4040
2076
2.23
0.6
3890
2006
2.15
0.8
3620
1882
2.02
1.0
3227
1708
1.83
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
†.
Blower performance includes two-inch throwaway filters.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
"Turns Open" refers to the setting of the variable pitch motor sheave, where "0 Turns Open" is fully closed.
††.
W = Watts
TABLE 20: 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
0
ESP
††
CFM
BHP
W
0.4
4965
3485
3.74
0.6
4876
3416
3.66
0.8
4713
3291
3.53
1.0
4476
3116
3.34
1.2
4165
2898
3.11
1.4
3779
2646
2.84
1.6
3319
2372
2.54
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
†.
Blower performance includes two-inch throwaway filters.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
"Turns Open" refers to the setting of the variable pitch motor sheave, where "0 Turns Open" is fully closed.
††.
W = Watts
26
1
††
CFM
BHP
CFM
W
-
-
-
-
4005
1934
2.07
3790
3697
1790
1.92
3427
3324
1629
1.75
2972
-
-
-
-
1
††
CFM
BHP
CFM
W
4875
3150
3.38
4613
4651
2997
3.21
4359
4387
2823
3.03
4077
4084
2632
2.82
3768
3741
2427
2.60
3432
3359
2212
2.37
3069
-
-
-
-
**
TURNS OPEN
2
3
††
††
BHP
CFM
W
W
-
-
3896
1639
1698
1.82
3569
1508
1550
1.66
3152
1356
1380
1.48
-
-
-
-
-
-
**
TURNS OPEN
2
3
††
††
BHP
CFM
W
W
2739
2.94
4322
2374
2582
2.77
4038
2220
2417
2.59
3719
2059
2245
2.41
3365
1892
2070
2.22
-
-
1895
2.03
-
-
-
-
-
-
035-17311-003-A-0704
* †
4
††
BHP
CFM
BHP
W
1.76
3688
1453
1.56
1.62
3333
1330
1.43
1.45
-
-
-
-
-
-
-
-
-
-
-
* †
4
††
BHP
CFM
BHP
W
2.55
4156
2106
2.26
2.38
3860
1966
2.11
2.21
3541
1827
1.96
2.03
3197
1691
1.81
-
-
-
-
-
-
-
-
-
-
-
-
Unitary Products Group
5
††
CFM
BHP
W
3447
1268
1.36
3057
1147
1.23
-
-
-
-
-
-
-
-
-
5
††
CFM
BHP
W
3907
1860
1.99
3590
1724
1.85
3242
1584
1.70
-
-
-
-
-
-
-
-
-
-
-
-