TECHNICAL GUIDE R-410A SPLIT-SYSTEM AIR HANDLERS MILLENNIUM™ ND360, 480 & 600 30 - 50 Ton 60 Hertz ND600 AIRHANDLER & M1CZ600 EVAPORATOR SECTION ® Description These air handling units are completely assembled units, including a well-insulated cabinet, a DX cooling coil with copper tubing, aluminum fins, expansion valve(s), distributor(s), 2”...
Nomenclature Configured Split Air Handler Model Number Nomenclature Product Category N = Split System, Air Handler, AC R-410A Product Identifier D = Standard Efficiency, 4-Pipe (30-50T) Nominal Cooling Capacity - MBH 360 = 30 Ton 480 = 40 Ton 600 = 50 Ton Heat Type &...
BAS Control: York Commercial Comfort System (YCCS) provides split system integration for YCCS single zone, change-over bypass and VAV systems. Easy Service: Serviceable expansion valves are provided on every unit.
Guide Specifications MILLENNIUM™ Split System Air-Cooled Air Handler Models: NC300 and ND360, 480 and 600 General Units shall be manufactured by Johnson Controls, Unitary Products Group in an ISO 9001 certified facility. These factory-assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, expansion valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a...
Page 6
628767-YTG-C-0910 The Installer Shall: Furnish condensing units in accordance with the performance schedules shown on the plans. Install each unit as shown on the plans in accordance with the manufacturer's recommendations and all applicable national and local codes. Unit Operating Characteristics Unit shall be capable of starting and running at 125º...
Physical Data ND360, 480 & 600 Physical Data Component Nominal Tonnage DIMENSIONS (inches) Length Width Height WEIGHTS (lb) Unit Shipping Unit Operating With 5 hp Motor and Drive 7.5 hp Motor and Drive 10 hp Motor and Drive INDOOR BLOWER Diameter x Width Qty.
628767-YTG-C-0910 Unit Limitations Air Handling Unit Limitations Model Power Supply Voltage 208/230-3-60 ND360 460-3-60 575-3-60 208/230-3-60 ND480 460-3-60 575-3-60 208/230-3-60 ND600 460-3-60 575-3-60 Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils. Cooling and Heating Ratings Cooling Ratings Condensing Unit Only...
Air Handling Unit and Hot Water Coil Accessory Heating Capacity ND360 / 1HW0406, ND480 & ND600 / 1HW0407 UNIT HOT WATER MODEL COIL MODEL ND360 1HW0406 ND480 1HW0407 ND600 These capacities do not include any blower motor heat. NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM. Hot Water Coil Capacity Correction And Pressure Drop Vs GPM HOT WATER COIL MODEL 1HW0406...
628767-YTG-C-0910 Air Handling Unit and Steam Coil Accessory Heating Capacity ND360 / 1NF0454 UNIT STEAM COIL MODEL MODEL ND360 1NF0454 These capacities do not include any blower motor heat. Steam Coil Capacity Correction Factors For High Steam Pressure STEAM PRESSURE (PSIG) CAPACITY CORRECTION FACTOR NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH CAPACITY (MBH) @ 2 PSIG...
Static Resistance Static Resistance Model ND360 ND480 ND600 Sound Performance Indoor Sound Power Levels Blower Model (Tons) (IWG) ND360 12000 0.75 (30) ND480 16000 0.80 (40) ND600 20000 1.13 (50) These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values provided are to be used for reference only.
628767-YTG-C-0910 Electrical Data Electrical Data UNIT VOLTAGE MODEL (3PH-60HZ) 16.7 15.2 24.2 ND360 30.8 24.2 ND480 30.8 30.8 ND600 46.2 MAX. FUSE CIRCUIT SIZE AMPACITY (Amps) Johnson Controls Unitary Products...
628767-YTG-C-0910 Weights And Dimensions Corner Weights & Center of Gravity ND360, 480 & 600 Unit Evaporator Blower Section Section Model Drive HP Cabinet Cabinet Wt (lb) Wt (lb) Vertical Airflow ND360 ND480 ND600 M1CZ600 Horizontal Airflow ND360 ND480 908.5 ND600 908.5 M1CZ600 Operating weight includes ND600 Airhandler and M1CZ600 Evaporator Coil Combined.
Page 23
22.5 19.0 RETURN 33.2 Unit Dimensions ND360 Johnson Controls Unitary Products 62.4 22.0 SUPPLY Ø0.88 KO 57.7 ELECTRIC HEAT CONNECTION FRONT RETURN 95.6 100.1 628767-YTG-C-0910 22.0 SUPPLY 4X Ø0.88 KO CONTROLS CONNECTION 15.9 SIDE 74.7 Ø1.125 SUCTION CONNECTION Ø0.88 DRAIN CONNECTION Ø1.125 SUCTION 0.63...
Page 24
628767-YTG-C-0910 HORIZONTAL CONFIGURATION RETURN SUPPLY 73.3 74.0 Unit Dimensions ND360 (Continued) Johnson Controls Unitary Products...
Page 25
60.5 20.6 22.0 19.0 SUPPLY FRONT 44.0 RETURN 44.7 40.5 Unit Dimensions ND480 Johnson Controls Unitary Products 22.0 SUPPLY RETURN 0.63 98.5 103.1 105.1 628767-YTG-C-0910 4X Ø0.88 KO CONTROLS CONNECTION SIDE 89.4 Ø1.375 SUCTION Ø1.375 SUCTION CONNECTION SYSTEM 2 45.4 Ø0.88 LIQUID CONNECTION SYSTEM 1...
Page 26
628767-YTG-C-0910 HORIZONTAL CONFIGURATION RETURN SUPPLY 88.2 88.8 Unit Dimensions ND480 (Continued) Johnson Controls Unitary Products...
Page 27
61.7 18.5 23.0 24.9 SUPPLY SUPPLY 45.4 44.0 Unit Dimensions ND600 Johnson Controls Unitary Products 103.1 23.0 SUPPLY FRONT SUPPLY 628767-YTG-C-0910 Ø0.88 KO CONTROLS CONNECTION Ø1.13 KO CONTROLS CONNECTION Ø1.38 KO CONTROLS CONNECTION DETIAL A SCALE 0.375 (2X TYP) SEE DETAIL A SIDE 45.5...
Page 28
628767-YTG-C-0910 53.7 FRONT RETURN 54.4 49.5 Unit Dimensions M1CZ600 Evaporator Section RETURN 98.5 103.1 105.1 SIDE Ø0.88 LIQUID CONNECTION SYSTEM 1 Ø0.88 LIQUID CONNECTION SYSTEM 2 Ø2.13 SUCTION CONNECTION Ø2.13 SUCTION SYSTEM 1 CONNECTION Ø.88 DRAIN SYSTEM 2 CONNECTION 53.7 Johnson Controls Unitary Products 10.2 27.6...
Page 29
FRONT SUPPLY RETURN 103.1 105.1 RETURN Unit Dimensions ND600 Airhandler & M1CZ600 Evaporator Coil Johnson Controls Unitary Products VERTICAL CONFIGURATION SUPPLY RETURN 99.0 97.8 54.4 HORIZONTAL CONFIGURATION NAMEPLATE 97.2 98.4 628767-YTG-C-0910 SIDE 45.5 53.7 SUPPLY...
Page 30
628767-YTG-C-0910 Unit Connection Sizes Model Dimensions (inches) Length Width Height System Data No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.) Power Wiring Knockout Control Wiring Knockout Drain Line Blower Outlet Number Width Length Return Air Inlet Width Length Minimum Clearances Top with Supply Air Opening...
Page 31
Dimensions Steam Coil Dimensions Steam Coil COIL UNIT MODEL MODEL 1NF0454 ND360 Coils are field-installed between the evaporator coil and the blower section of the unit. Dimensions Base Section Johnson Controls Unitary Products DIMENSIONS 100-1/8 37-7/8 4-3/8 Dimensions Base Sections BASE MODEL 1BS0406...
628767-YTG-C-0910 Unit Mounting ND360, 480 & 600 The ND Series evaporator units may be suspended from joists with isolation type hangers or hooks. Suspension accessories 1HH0403 (ND360), 1HH0404 (ND480) and 1HH0405 (ND600 Air Handler with M1CZ600 Evaporator Section) may be ordered separately. All Suspension accessories include three...
Page 33
NOTE: The following illustration shows how the channels 3/8 NUT (USED AS SPACER) ND360/ND480 Details For Securing Suspension Channels ND600 & M1CZ600 Weight Distribution With Suspension Application Johnson Controls Unitary Products should be secured to the unit using the hardware provided with the suspension accessory.
Page 34
628767-YTG-C-0910 ND600 Mounting Detail When arranged horizontally, the ND600 airhandler and M1CZ600 evaporator coil can be suspended from joists with hanger rods using a suspension accessory. The suspension channels require no drilling or cutting. Each channel has enough holes in its bottom flange for: Four bolted connections to the evaporator coil section.
Page 35
Unit Mounting Dimensions UNIT 69-1/4 ND360 ND480 ND600 Johnson Controls Unitary Products DIMENSIONS, INCHES 49-1/16 50-9/16 51-1/2 628767-YTG-C-0910 26-5/8...
628767-YTG-C-0910 Typical Field Wiring Diagrams Typical Field Wiring Diagram ND360/480 Evaporator Units, ND600 Air Handler and M1CZ600A Evaporator Coil when Matched with YD360/480/600 Condenser NOTE: On non ND evaporator models, isolation relays must be installed to avoid overloading on 75VA transformers on the condensing unit.
Page 37
Typical Liquid Line Solenoid Wiring Johnson Controls Unitary Products Standard Terminal Block on NC300, ND360/480 and ND600 with M1CZ600A models. On non NC/ND models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit. Primary side of transformer connect to line side of power supply.