Table 7. Power consumption examples per enclosure
Model and type PSU
5147-092
expansion
enclosure with
92 HDDs in a
primary
enclosure. 2
SSDs and 90
HDDs in non-
primary
enclosures,
3.5-inch form
factor SAS drive
slots
Note: These measurements are presented as an example. Measurements that are obtained in other
operating environments might vary. Conduct your own testing to determine specific measurements for
your environment.
Each Model 092 expansion enclosure contains two PSUs for redundancy. The total power consumption
values represent the total power that is drawn by both PSUs.
Environmental requirements
System airflow is from the front to the rear of each enclosure:
• Airflow passes between drive carriers and through each enclosure.
• The combined power and cooling module exhausts air from the rear of each canister.
Ensure that your environment falls within the ranges that are listed in Table 8 on page 28.
Table 8. Temperature requirements
Environment
Operating
Non-operating
Storage
Shipping
Note:
• – Max Ambient Temperature Environment = 32C / 950 m
– Max Altitude Environment = 25C / 3,050 m
– Decrease the maximum air temperature by 1 degree C per 300 m above 950 m.
• The maximum ambient operating temperature when using an optical cable or discrete optical
transceiver is 32C, which includes all Ethernet (100Gb) cables and InfiniBand (100Gb EDR) that are
28 IBM Elastic Storage System 5000: Model 092 Hardware Guide
Input power
requirements
180 V to 264 V
single phase AC
1200 W (2)
at a frequency
of 47 Hz to 63
Hz
Ambient temperature
1
5°C to 32°C
(41°F to 90°F)
1°C to 50°C
(34°F to 122°F)
1°C to 60°C
(34°F to 140°F)
-40°C to 60°C
(-40°F to 140°F)
Maximum
Maximum
input current
power output
(W)
6.12 A
Requires a C20
power socket
(C20 PDU)
1200
Altitude
2, 3
0 - 3048 m
(0 - 10000 ft)
-305 to 12192 m
(-1000 to 40000 ft)
Caloric value
(BTU/hr)
4096
Relative humidity
8% to 80% non-
condensing
8% to 80% non-
condensing
5% to 80% non-
condensing
5% to 100% condensing,
but not precipitating