Field Wiring; General; Unit Disconnect; Return Air And Outside Air Sensor - McQuay SWT C Series Installation And Maintenance Manual

Self-contained air conditioning system vintage sizes 18 thru 40
Table of Contents

Advertisement

Field Wiring

General

Wiring must comply with all applicable codes and ordi-
nances. The warranty does not cover equipment failures
caused by or contributed to wiring not in accordance with
specifications. An open fuse indicates a short, ground or
overload. Before replacing a fuse or restarting a compressor
or fan motor, the trouble must be found and corrected. Use
copper wire for all power lead terminations. Contact factory
for information concerning aluminum wire power lead ter-
minations.
A single power terminal block is provided as standard and
wiring within the unit is done in accordance with the
National Electric Code. All branch circuits within the control
panel are individually fused. A single field supplied discon-
nect is required or a unit mounted nonfused disconnect can
be ordered with the unit.
Table 7. Compressor Motors
A 7/8" knockout is located on the right-hand unit upright for
locating unit power entry. 24V field connections are suitable
for Class II wiring.

Unit Disconnect

Disconnecting means are addressed by Article 440 of the
National Electric Code (NEC) which requires disconnecting
means capable of disconnecting air conditioning and refrig-
erant equipment including motor-compressors, and control-
lers, from the circuit feeder." The disconnect switch should
be selected and located within the NEC guidelines. Location
requirements per NEC are that the disconnect be located in a
readily accessible position within sight (50 feet) of the unit.
A factory mounted nonfused disconnect is available.
Table 7. Compressor Motors
208/60/3
Compressor
HP
RLA
LRA
6
17.9
156.0
10
31.2
239.0
13
35.6
350.0
Table 8. Electric Heaters
208V/60HZ/3PH
SWP UNIT SIZE
kW
MBH
018 - 040
27.8
94
IM709
230/60/3
RLA
LRA
16.2
156.0
8.1
28.2
239.0
14.1
32.0
350.0
16.0
230V/60HZ/3PH
FLA
kW
MBH
FLA
77.2
34
116
85.6
Return Air and Outside Air Sensors
All units are provided with a return air sensor. The outside
air sensor is optional and can be ordered with the unit. The
return air sensor is connected to the input control board and
is coiled up and placed in the control box of the unit for ship-
ment. The return air sensor must be field installed in the
return air stream for proper unit operation. The outside air
sensor is shipped loose in a package and is located on the
floor of the fan section. The mixed air temperature sensor is
already installed at the inlet of the unit.
The sensors must be mounted in areas that are exposed to
representative temperature conditions. The sensor should be
mounted at a position that has good air mixing and does not
have stratification. The sensor can be mounted in the duct-
work using a grommet, see Figure 17.
Figure 17. Return/Outside Air Sensor Mounting
Ductwork
The return air sensor is connected to the unit's input board at
location AI4, see IM710. The outside air sensor is field
wired to terminal strip TB2. The sensor is to be connected at
terminals 124 and 125.
400/50/3
460/60/3
RLA
LRA
RLA
70.0
8.1
125.0
14.1
158.0
16.0
400V/50HZ/3PH
460V/60HZ/3PH
kW
MBH
FLA
kW
25.7
88
37.2
34
Sensor
Grommet
575/60/3
LRA
RLA
70.0
6.5
54.0
125.0
11.3
80.0
158.0
12.8
125.0
575V/60HZ/3PH
MBH
FLA
kW
MBH
116
42.8
34
116
LRA
FLA
34.2
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Swt018cSwt023cSwt028cSwt035cSwt040c

Table of Contents