6.3

Operation parameters related to remote system

Table 6.4 shows operation parameters related to remote system.
Only hard error of master module is informed to CPU. When hard error (HERR) occurs in master module, CPU detect remote
error, and error code "43" is set in CPU. You can select whether to continue running or not by setting this parameter with
programming software.
Because
disagreement of I/O allocation and slave station error is not informed to CPU, CPU doesn't detect remote error in this
CPU continues running regardless of the setting of the remote transmission mode.
case. Therefore
No.
Item
Operation mode
1
of CPU at error
2
Remote
transmission
mode
3
(Note 1) When the error is detected in check with reverse double-transmission, only illegal data are abandoned and last
correct data is maintained. Regardless of this error detection, communication between master and slaves continues.
(Note 2) Please refer to Section 6.5 when you want to stop running of CPU when power supply OFF, breaking down, and
disconnecting about slave stations.
6.4

Function of reset switch

When hard error (HERR) of communication error occurs in master module (EH-TRMME) or slave module
(EH-TRMLE), you can reset the error by pushing reset switch in front side of the module. However error is
indicated again if error factor is not canceled.
The setting of the rotary switch and the DIP switch is read only when the power supply is turned on. However
pushing reset switch allows remote module to restart with new setting even if you don't turn on power supply again.
Please note that error information shown in Table 6.3 are not cleared by pushing the reset switch in master module
and slave module. These error information are
cleared by only turning on again the power supply.
If you push reset switch of master module, the
communication module transmission error (error
code "55") occurs in CPU module because of no
response to CPU during restart processing. This
error is warning in classification of error, and CPU
can continue to running. Please clear the special
internal output related to this error if necessary.
Table 6.4 Operation parameters related to remote system
Specifies run
At a occurrence
permission/inhibition while
error has occurred in remote
of remote error
module.
When I/O allocation of remote
At a
module is disagreement, it
disagreement of
specifies whether remote is
I/O allocation
abnormal.
While error has occurred in
The slave station
remote slave station, it
error of remote
specified whether remote is
abnormal.
Chapter 6
Error indication and Countermeasure
Description
Error detection
Hard error in master
(Checked When
turning on power
Check with reverse
double-transmission
Reset switch
Fig 6.1 Reset switch of remote module
6 – 3
Operation of compact remote
Error information to
Available
(It operates according
to the setting of the
supply)
operation parameter.)
Not available
No detection
(CPU continues
running regardless of
the setting of the
remote transmission
mode.) (Note 2)
(Note 1)
RESET
Master module
Slave module
(EH-TRMME)
(EH-TRMLE)
CPU
RESET