Special Internal Outputs In Cpu Module - Hitachi HIDIC EH150 EN-TRMME Applications Manual

Compact remote module
Table of Contents

Advertisement

Chapter 6
Error indication and Countermeasure
6.2

Special internal outputs in CPU module

Remote refresh time and information about time-out error are stored in special internal outputs as shown in Table
6.3 when I/O assignment of master module of compact remote is "REMOTE 2".
Please note that the information to be stored is different from the other remote system. And pay attention that these
information are not stored when I/O assignment of master module is "Word 4W/4W".
■ Special internal outputs number of each master
Master No.1: WRF080~WRF097
Master No.2: WRF098~WRF0AF
Master No.3: WRF0B0~WRF0C7
Master No.4: WRF0C8~WRF0DF
Table 6.3 Special internal outputs concerning with remote in CPU module
Special internal outputs number
Master
Master
Master
No.1
No.2
No.3
WRF080
WRF098
WRF0B0
WRF081
WRF099
WRF0B1
WRF082
WRF09A
WRF0B2
WRF083
WRF09B
WRF0B3
WRF084
WRF09C
WRF0B4
WRF085
WRF09D
WRF0B5
WRF086
WRF09E
WRF0B6
WRF087
WRF09F
WRF0B7
WRF088
WRF0A0
WRF0B8
WRF089
WRF0A1
WRF0B9
WRF08A
WRF0A2
WRF0BA
WRF08B
WRF0A3
WRF0BB
WRF092
WRF0AA
WRF0C2
WRF093
WRF0AB
WRF0C3
WRF094
WRF0AC
WRF0C4
WRF095
WRF0AD
WRF0C5
WRF096
WRF0AE
WRF0C6
WRF097
WRF0AF
WRF0C7
(Note 1) The transmission error in slave is time-out error detected when there is no response about same cannel from slave station
during 0.5 ms. And following information are stored in each bit.
k: 1 is set when time-out error is detected. Because it is not cleared even if the communication recovers, you can
know the presence of past error.
Error channel No.: Channel No. of the time-out error detected at the end is stored.
Number of times transmission error: The number of errors of the accumulation after the power supply on base unit
is turned on is stored. It returns to 0 when it exceeds to 255, and count is continued.
These error information are cleared by turning on again the power supply. Please note that these error information are not
cleared by pushing the reset switch in master module and slave module.
Master
No.4
WRF0C8
Assignment flag of slave
WRF0C9
WRF0CA
Detail information of transmission
WRF0CB
error in slave ST. No.0 (Note 1)
Detail information of transmission
WRF0CC
error in slave ST. No.1 (Note 1)
Detail information of transmission
WRF0CD
error in slave ST. No.2 (Note 1)
Detail information of transmission
WRF0CE
error in slave ST. No.3 (Note 1)
Detail information of transmission
WRF0CF
error in slave ST. No.4 (Note 1)
Detail information of transmission
WRF0D0
error in slave ST. No.5 (Note 1)
Detail information of transmission
WRF0D1
error in slave ST. No.6 (Note 1)
Detail information of transmission
WRF0D2
error in slave ST. No.7 (Note 1)
Detail information of transmission
WRF0D3
error in slave ST. No.8 (Note 1)
Detail information of transmission
WRF0DA
error in slave ST. No.15 (Note 1)
WRF0DB
I/O verify mismatch slot No.
WRF0DC
WRF0DD
Refresh time (Maximum)
WRF0DE
Refresh time (Minimum)
WRF0DF
Refresh time (Current)
Name
15
Bit number correspond to slave station number
Undefined
Undefined
I/O error slot No.
6 – 2
Contents of each bit number
14
8
7
(1: slave is assigned, 0: slave is not assigned)
0
0
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
Number of times
k
Error channel No.
transmission error
0
0
0
0
Remote refresh time (Maximum) (unit: ms)
Remote refresh time (Minimum) (unit: ms)
Remote refresh time (Current) (unit: ms)
0