Part 5: Review on Replacement of MR-J3-DU_ with MR-J4-DU_
Note 1. For the power supply specifications, refer to "Part 7: Common Reference Material".
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may
cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
required, slow the time to turn off the magnetic contactor.
3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing
the short bar across them. Refer to "Part 9: Chapter 7" for details.
4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the
converter unit and brake unit malfunction.
5. For 400 V class, a step-down transformer is required.
6. Contact rating: 1a contact, 110 V AC, 5 A/220 V AC, 3 A
Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting.
7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A
Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting.
8. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to
section 7.3.)
9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the converter unit.
10. Always connect BUE and SD terminals. (factory-wired)
11. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of
the drive unit.
12. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-J4-
_(-RJ). Refer to each servo amplifier instruction manual.
5 - 64