Mitsubishi Electric 800 Series Instruction Manual page 25

Functional safety, compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Output frequency
Pr.S006
Pr.S018
Overspeed time
counter
SLS1 command
(SLS1C)
SLS1 output
(SLS1S)
STO output
(STOS)
 Changing the frequency command automatically when the SLS function
is activated (Pr.S005 = "1")
The following shows the operation example when only the SLS1 function is activated (Pr.S005 = "1").
• When Pr.S005 = "1", the frequency command is changed to the value set in Pr.S014 after the SLS1 function is activated.
NOTE
• The priority of the frequency commands given by the external signals is as follows: SLS function > JOG operation > multi-
speed operation > terminal 4 analog input > terminal 2 analog input.
• The maximum frequency settings in Pr.1 and Pr.18 are valid, and the minimum frequency setting in Pr.2 is invalid.
Pr.S010
ON
ON
ON
Pr.S010
Output frequency
Pr.S006
Pr.S014
SLS1 command
ON
(SLS1C)
SLS1 output
ON
(SLS1S)
STO output
ON
(STOS)
Actual motor speed
Speed monitoring
STO state
Time
Speed monitoring
3
Time
4
5
5
5
6
7
8
9
10
25
5. Safety Sub-Functions
5.3 SLS function