Download Print this page

Panasonic Tro-Reel 60A Operation Manual page 5

For indoor and outdoor use

Advertisement

10
Name
Contents of inspection
Isn't there the slack of a bolt for electric
wire connection of the feeding-in joiner ?
Are not there the cracks and damaged
on a resin part?
Are not there a loser of the cover part,
the falling off?
Is the hanger installation pace equal to
or less than 4m?
As for the curve department and the
hanger installation of both ends of the
terminal tightening insulator, is the pace
equal to or less than 500mm?
Is not there the slack of the installation
bolt?
Are not there the cracks and damaged
on a resin part?
Is the center fixed insulator attached so
that the gap between the ducts may be
set to 15mm ± 5mm?
Is the coil spring set definitely?
Length of the coil spring L =115-
125mm
 
 
Does not a nut (a double nut) of the coil
spring part have the slack?
Isn't there the slack of a bolt for electric
wire connection of the feeding-in joiner ?
Are not there the cracks and damaged
on a resin part?
Are not there a loser of the cover part,
the falling off?
Are not there the cracks and damaged
on a resin part?
Are not there a loser of the cover part,
the falling off?
A r e t h e i n s t a l l a t i o n d i m e n s i o n s
clearance?
Are not there a loser of the cover part,
the falling off?
D o e s n o t t h e r e s i n p a r t h a v e t h e
abrasion?
Are not there the cracks and damaged
on a resin part?
Retighten
When damage and crack occurred in it,
please change it.
Please install the cover.
Please install a hanger to become equal
to or less than 4m.
Please install a hanger to become equal
to or less than 500mm.
Retighten
When damage and crack occurred in it,
Please change it.
Please adjust so that the gap between
the ducts is set to 15mm ± 5mm.
Please adjust it to reasonable length.
L  
Retighten
Retighten
When damage and crack occurred in it,
Please change it.
Please install the cover.
When damage and crack occurred in it,
Please change it.
Please install the cover.
Please revise it to dimensions in the
clearance
A 
C  
Please install the cover.
When I am worn, please change
When damage and crack occurred in it,
Please change it.
Remedy
Ambient temperature
the case of less than 10℃
the case of 11℃~ 40℃
A
B
5mm
length 10 ~ 30mm
lower
ー 45 ー
Result Measures
L
115mm
125mm
C
7mm
lower
Inspection cycle (standard)
Once
every
3 to 6
months

Advertisement

loading

This manual is also suitable for:

Tro-reel 150aTro-reel 200aTro-reel 300a