Safety configuration
10.8 Configuring Safety Integrated plus (F-PLC)
Acceptance of the system
Information on the acceptance of a safety configuration with controller can be found in the TIA
Portal information system under "Acceptance of the system".
Note
Error-free hardware and software transmission
Error-free HW and SW transmission is the prerequisite for the creation of the safety printout for
acceptance purposes. Only then is it assured that all consistency checks have been performed
and therefore the safety printout created for a consistent project.
10.8.5

Checking the PROFIsafe address

Unique PROFIsafe address
To ensure safe communication, unique PROFIsafe addresses are required throughout the
CPU and the network.
For this reason, it is also necessary that you check the settings of the PROFIsafe addresses
carefully.
Unique PROFIsafe addresses
You must ensure the unique assignment of the PROFIsafe address throughout the network
and the CPU.
● The fail-safe I/O of PROFIsafe address type 1 is addressed clearly by its fail-safe
● The fail-safe destination address of the fail-safe I/O (drive units in this case) must be
● Note also the corresponding documentation in the TIA Portal online help in the section
During compilation of the safety program, a warning indicates the importance of unique
PROFIsafe addresses:
208
WARNING
destination address.
unique for the entire fail-safe I/O throughout the network and the CPU (system-wide). The
fail-safe I/O of PROFIsafe address type 2, e.g. modules of the ET 200SP type, must also
be taken into account.
"SIMATIC Safety - Configuration and programming".
SIN001 )
(
SINUMERIK STEP 7 Toolbox V15.1
Configuration Manual, 12/2018, A5E46279635B AA