Setting method [G] [WG]
■1-axis servo amplifiers with a capacity of 2.0 kW or less
If "0" (automatic) is set in [Pr. PC20.4 Input open-phase detection selection], the input open-phase detection function will be
disabled.
The input open-phase detection function is enabled by setting [Pr. PC20.4] to "1" (warning enabled) or "2" (alarm enabled). If
"1" (warning enabled) is set, [AL. 1E9 Open-phase warning] will be outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC20.4] to "2" (alarm enabled).
■1-axis servo amplifiers with a capacity of more than 2.0 kW
When [Pr. PC20.4 Input open-phase detection selection] is set to "0" (automatic), the input open-phase detection function is
enabled. If "0" (automatic) is set, [AL. 1E9 Open-phase warning] is outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC20.4] to "2" (alarm enabled).
■Multi-axis servo amplifiers with a capacity of 0.75 kW or less
If "0" (automatic) is set in [Pr. PC20.4 Input open-phase detection selection], the input open-phase detection function will be
disabled.
The input open-phase detection function is enabled by setting [Pr. PC20.4] to "1" (warning enabled) or "2" (alarm enabled). If
"1" (warning enabled) is set, [AL. 1E9 Open-phase warning] will be outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC20.4] to "2" (alarm enabled).
■Multi-axis servo amplifiers with a capacity of more than 0.75 kW
When [Pr. PC20.4 Input open-phase detection selection] is set to "0" (automatic), the input open-phase detection function is
enabled. If "0" (automatic) is set, [AL. 1E9 Open-phase warning] is outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC20.4] to "2" (alarm enabled).
Servo
Symbol
parameter
PC20.4
*COP7
Setting method [A]
■Servo amplifiers with a capacity of 2.0 kW or less
If "0" (automatic) is set in [Pr. PC27.4 Input open-phase detection selection], the input open-phase detection function will be
disabled.
The input open-phase detection function is enabled by setting [Pr. PC27.4] to "1" (warning enabled) or "2" (alarm enabled). If
"1" (warning enabled) is set, [AL. 1E9 Open-phase warning] will be outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC27.4] to "2" (alarm enabled).
■Servo amplifiers with a capacity of more than 2.0 kW
When [Pr. PC27.4 Input open-phase detection selection] is set to "0" (automatic), the input open-phase detection function is
enabled. If "0" (automatic) is set, [AL. 1E9 Open-phase warning] is outputted when the input open phase occurs. To generate
[AL. 139 Open-phase error] when an open phase occurs, set [Pr. PC27.4] to "2" (alarm enabled).
Servo
Symbol
parameter
PC27.4
*COP6
Name
Input open-phase detection
selection
Name
Input open-phase detection
selection
Outline
Enable or disable the detection of input open-phase detection function.
0: Automatic (initial value)
1: Warning enabled
2: Alarm enabled
3: Disabled
Outline
Enable or disable the detection of input open-phase detection function.
0: Automatic (initial value)
1: Warning enabled
2: Alarm enabled
3: Disabled
4.17 Disconnection/incorrect wiring detection function
4 APPLICABLE FUNCTIONS
4
285