3) Room temperature sensor control for heating
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
Function number
31
4) Auto restart
Enables or disables automatic restart after a power interruption.
Function number
40
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
5) Room temperature sensor switching
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number
42
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
44
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
46
11-1. Function settings by using remote controller
Setting value
00
01
02
03
Setting value
00
01
Setting value
00
01
Setting value
00
01
02
03
Setting value
00
01
02
- 27 -
Setting description
Standard
Lower control
Slightly higher control
Higher control
Setting description
Enable
Disable
Setting description
Indoor unit
Both
Setting description
A
B
C
D
Setting description
Operation/Stop mode
(Setting prohibited)
Forced stop mode
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting