Download Print this page

Mitsubishi Electric PAC-IF01MNT-E Installation Manual page 3

A-m converter

Advertisement

2. Wiring method for M-NET
Caution for wiring
1 Never supply voltage 208V-230VAC to the terminals for M-NET transmission. If the voltage is supplied,
it can break the electronic parts on the M-NET board.
2 Use the shielded cable (CVVS, CPEVS, MVVS) of 1.25mm² (AWG 16) with 2 wires (polarity is
not a concern) for the transmission cable.
Never use transmit wires of different system with a cable which contains multi wires.
The communication of transmit signals will not work properly and it can cause wrong operation.
3 The power consumption coefficient
w1 "Power consumption coefficient" is a coefficient to calculate the relative power
consumption of the devices that receive power through the M-NET transmission cable.
System
A
controller
B
200m (656 ft) or less
MA : MA remote controller
RC :Wireless remote controller
w1
of the M-NET board is "1".
Power supply
unit
for transmit
A
B
S
Outdoor unit
A unit
M-NET board
M1
M2
B unit
S
C unit
D unit
E unit
w Ex)MXZ-5C42NA indoor units maximum connection.
Outdoor unit
M1
M-NET board
M2
A unit
S
B unit
C unit
D unit
w Ex)MXZ-4C36NA indoor units maximum connection.
3
MA
Indoor unit
MA
Indoor unit
MA
Indoor unit
MA
Indoor unit
RC
Indoor unit
MA
Indoor unit
Indoor unit
MA
MA
Indoor unit
RC
Indoor unit

Advertisement