14.9 Auto Restart Control

When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
14.10

Indication Panel

LED
Color
Light ON
Light OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.

14.11 ECO Mode Operation

This operation is use to reduce electrical power consumption by adjusting the set temperature.
ECO operation starts when the ECO button is pressed during cooling or dry operation.
During Cooling/Dry ECO operation, target setting temperature will be adjusted by +2°C. Internal setting
temperature limit shift to maximum 35°C (maximum 33°C + 2°C Economy shift).
During ECO operation, all indicators includes ECO indicator will be dimmed. The brightness level is equivalent to
indicator dim function.
Powerful, Quiet and ECO could not be operated at the same time. The unit will follow the latest setting of these
three operations.
The ECO operation stops when:
1
POWERFUL/QUIET button is pressed.
2
Operation OFF.
3
Received ECO signal from remote control again.
4
Received either Powerful or Quiet operation signal from remote control.

14.12 HA Terminal (HAJEM-A)

Enable digital connection from indoor unit to external devices.
Control items:
1
Start/stop input.
2
Start/stop signal output.
Condition
1
1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.
(1 pulse signal: shortage status 200~300msec)
2
3-4 (Static output): 5V output during the unit ON. No output at OFF.
POWER
Green
Operation ON
Operation OFF
200~300msec
ON/OFF input
(Pin 1-2)
Monitor output
(Pin 1-2)
Unit condition
TIMER
POWERFUL
Orange
Timer Setting ON
POWERFUL Mode ON
Timer Setting OFF POWERFUL Mode OFF
+5V
ON
OFF
105
ECO
Orange
Orange
ECO ON
ECO OFF
ON