Insulating The Refrigerant Tubing; Taping The Tubes - Panasonic S-36PT2E5B Installation Instructions Manual

Hide thumbs Also See for S-36PT2E5B:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
For the flare nuts at tubing connections, be sure to use the
flare nuts that were supplied with the unit, or else flare nuts
for R410A, R32 (type 2). The refrigerant tubing that is used
must be of the correct wall thickness as shown in the table
below.
Tightening torque
Tube diameter
(approximate)
14 – 18 N · m
ø6.35 (1/4")
{140 – 180 kgf · cm}
34 – 42 N · m
ø9.52 (3/8")
{340 – 420 kgf · cm}
49 – 55 N · m
ø12.7 (1/2")
{490 – 550 kgf · cm}
68 – 82 N · m
ø15.88 (5/8")
{680 – 820 kgf · cm}
Because the pressure is approximately 1.6 times higher than
conventional refrigerant R22 pressure, the use of ordinary
flare nuts (type 1) or thin-walled tubes may result in tube
rupture, injury, or asphyxiation caused by refrigerant leakage.
In order to prevent damage to the flare caused by over-
tightening of the flare nuts, use the table above as a guide
when tightening.
When tightening the flare nut on the liquid tube, use an
adjustable wrench with a nominal handle length of 200 mm.

5-3. Insulating the Refrigerant Tubing

Tubing Insulation
Must ensure that pipe-work shall be protected from physical
damage.
● Thermal insulation must be applied to all units tubing,
including distribution joint (field supply).
* For gas tubing, the insulation material must be heat
resistant to 120°C or above. For other tubing, it must be
heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH
70%, increase the thickness of the gas tubing insulation
material by 1 step.
Insulation of the flare nuts
Attach the flare insulator (supplied) just like wrapping around
the flare nut (supplied). Match the both slits of flare insulators
for gas and liquid tubes facing upward. Tightly attach the end of
the flare insulators to the tube cradle without any space. Then
clamp the flare insulator with the clampers about 20 mm away
from both ends.
Facing upward
Liquid tubing
Gas tubing
Tube thickness
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Flare insulator (for gas tube)
Flare insulator
(for liquid tube)
Tube cradle
Additional Precautions For R32 Models.
Ensure to do the re-flaring of pipes before connecting to
units to avoid leaking.
To prevent the ingress of moisture into the joint which could
have the potential to freeze and then cause leakage, the joint
must be sealed with suitable silicone and insulation material.
The joint should be sealed on both liquid and gas side.
Insulation material and silicone sealant. Please ensure
there are no gaps where moisture can enter the joint.
Silicone Sealant must be neutral cure and ammonia free. Use of
silicon containing ammonia can lead to stress corrosion on the
joint and cause leakage.
Taping the flare nuts
Wind the white insulating tape around the flare nuts at the gas
tube connections. Then cover up the tubing connections with
the flare insulator, and fill the gap at the union with the supplied
black insulating tape. Finally, fasten the insulator at both ends
with the supplied vinyl clamps.
Insulator (not supplied)
Clamper
Outdoor unit
side
About 20 mm
N OT E
Tighten the clampers to prevent any condensation that may
occur as the copper tubing is exposed.
Insulation material
The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must not
easily absorb moisture.
CAUTION
After a tube has been insulated, never try to bend it into
a narrow curve because it can cause the tube to break or
crack.
Never grasp the drain or refrigerant connecting outlets
when moving the unit.

5-4. Taping the Tubes

(1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped together with
armoring tape in 1 bundle. To prevent condensation from
overflowing the drain pan, keep the drain hose separate
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you
wrap the tubing, overlap half of each previous tape turn.
18
Without any space
Flare nut
Clamper
Tube cradle
(supplied)
Indoor unit
side
Insulating tape
About 20 mm
(supplied)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents