Note
Information on the dimensioning of the fuses in the higher-level plant circuits
A fuse, which is designed for a tripping current of typical 6.3 A, is integrated in the power
supply of the IPC. Pulse current are also taken into consideration by the "time lag" type. In
the case of fault, this fuse ensure the correct separation of the device from the power supply.
It is recommended to use a fuse of at least 6.3 A for the protection of the higher-level power
supply circuit in addition to the power requirement of the additional devices that are also
supplied through this circuit. The tripping characteristic of the higher-level protection must
hereby take into consideration the starting currents of the IPC and those of the other
devices.
8.4.4

AC power supply, redundant

Voltage
+12 V
+12 V
–12 V
+5 V
+3.3 V
+5 V aux
1
2
The inrush current of a plug-in module is:
● ≤ 210 A for 1.65 ms
8.4.5

Technical specifications of the telescopic rails

Ultimate load per pair
Full extraction length
Rail thickness
Mounting screws
See also
Dimension drawing of the telescope rails (Page 147)
SIMATIC IPC547G
Operating Instructions, 04/2020, A5E49948632-AA
The total output of the +5 V and +3.3 V voltage must be ≤ 100 W.
The total current of the +12 V voltage must be ≤ 25 A.
Max. current
16 A
2
16 A
2
0.5 A
20 A
1
20 A
1
3.0 A
≥ 30 kg
≥ 470 mm
≤ 9.7 mm
M5 x 6 mm
The mounting screws of the telescopic rails may not protrude by
more than 5 mm into the enclosure.
Technical specifications
8.4 Technical specifications
Voltage stability
± 5%
± 5%
± 10%
± 5%
± 5%
+5%, -3%
159