Siemens OpenAir G Series Manual page 6

Damper actuator modbus rtu

Advertisement

Register 769 "Status"
Status
Bit 00
Bit 01
Bit 02
Bit 03
Bit 04
Bit 05
Supported function codes
Function codes
03 (0x03)
04 (0x04)
06 (0x06)
16 (0x10)
Notes
Safety
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
Mounting
● Do not open the damper actuators
● Do not use the accessory mounting holes for fixation of the damper actuators
Mounting
Mounting positions
IP54 protection in following mounting positions
1)
2)
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following internet address:
http://siemens.com/bt/download
6 / 12
Siemens
Smart Infrastructure
1 = Local override
1 = Backup mode active
1 = reserved
1 = reserved
1 = Device jammed
1 = Nom. lifetime exceeded
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple registers (Limitation: Max. 120 registers within one message)
Caution
Observe national provisions and comply with the appropriate safety regulations.
Not to be used for fixation of the actuator, use anti-rotation-bracket instead.
Bit 06
1 = Adaption done
Bit 07
1 = Adaption in progress
Bit 08
1 = Adaption error
Bit 09
1 = Selftest failed
Bit 10
1 = Selftest passed
Bit 11
1 = Invalid configuration
1)
Accessory mounting holes
Cf. mounting instr. A6V10409478
A6V10881141_en--_c