Firmware update

12.1
Updated at the control panel with WINFEM via BUS-2
Index .10 und .17). With an update via BUS-2, a tamper signal may be transmitted to the
control panel, as the EU activates a reset after the update.
12.2
Update at the EU via ST18:
Conditions:
-
Min. WINFEM-100.10, V04 with service pack 2 and software tool FFAST from version V03.03.
-
PC adapter cable for IK3 EU BUS-2, Item no. 023202 (and USB-Adapter-Box, Item no.
013467.10 if required, see below).
Update:
-
Connect PC/laptop to the EU according to illustration below.
-
Bridge the contacts from jumper JP22 while the EU is de-energized. If necessary, use a jumper
plug from
JP15
of the EU.
-
Apply operating voltage U_b 12 V DC (BUS-2 not required).
-
The boot loader is now activated, the green LED flashes every 500 ms.
-
Start WINFEM. The update is started via Tools - FFAST - Firmware download.
-
When the procedure is finished, disconnect the operating voltage, remove the plug at JP22 and
if necessary, re-connect at the original position.
-
Re-connect the operating voltage and BUS-2 to the EU.
BUS-2 not
required
+12 V DC
U_b
0 V
Mounting and Connection Instructions IK3 Evaluation Unit BUS-2
JP15
serial interface (COM1 or COM2)
or USB interface via
USB-Adapter-Box
RS-232
9-pole
Sub D
Adapter cable 023202
(only for control panels with
Buzzer
JP22
RS-232
ST18
LD1
LD2
yellow green
Firmware downloaded
allways off
LD1
LD2
Testing firmware after update
LD1
LD2
Faulty firmware
LD1
LD2