Vav compact controller knx / pl-link
Hide thumbs

Advertisement

Note
Settings and operating mode
Parameterization
Variable air volume
control (VAV)
Constant air volume
control (CAV)
4 / 10
Siemens
Building Technologies
For further information on settings, operating modes, and engineering and
commissioning workflows in the available system environments, please refer to
"Technical Basics" P3547.
OEM generally provide the basic configuration to VAV compact controllers,
especially the parameter
were the VAV compact controllers are used (i.e. PL-Link, KNX LTE-mode, KNX S-
mode). Overall system engineering and commissioning is based on this basic
configuration; accomplished using tools listed under "equipment combinations"
(p. 2).
The following parameters must be checked or set prior to commissioning:
Parameter
Setting
V
1...3,16
n
V
20...120 %
max
V
-20...100 %
min
r or L
Dir
Off or on
ADP
0...5000 m
Altitude
(Resolution 500 m)
VAV compact controllers operate in VAV mode when connected to the specified
power supply. The setpoint signal determines the operating range
Vmin [%]
Vmax [%]
3
The VAV compact controllers can be operated in CAV mode by setting the setpoint
value accordingly.
VAV compact controller KNX / PL-Link GDB181.1E/KN and GLB181.1E/KN
V . Configuration depends on the system environment
n
Description
Characteristic value for the air volume flow;
set by the manufacturer (OEM)
Maximum air volume flow
Minimum air volume flow
Air damper rotation (opening direction)
r = Clockwise (CW)
L = Counter clockwise (CCW)
Standard mode for air damper position
display (Mapping 0°...90°
Adaptive mode for air damper position
display (Mapping e.g. 0°...60°
Altitude level for differential pressure sensor 500 meters
1 Setpoint point
2 Actual value
3 Controlled area
Siemens factory
setting
1
100 %
0 %
r
Off
0...100 %)
0...100 %)
V
...
V
min
max
CE1N3547en
2016-01-29
.