Page 2
CANopen und CiA sind eingetragene Gemeinschaftsmarken der CAN in Automation e.V. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 2 of 196 TR - ECE - BA - DGB - 0147 - 02...
4.7.7.3 LSS identify non-configured remote slave Protokoll ..............35 4.7.7.4 LSS identify non-configured slave Protokoll................35 4.8 Geräteprofil ..........................36 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Page 4
8.17 Objekt 1021h: EDS abspeichern ..................55 8.18 Objekt 1022h: EDS Speicherformat ..................55 8.19 Objekt 1029h: Verhalten im Fehlerfall .................. 55 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 4 of 196...
Page 5
9.3.2.1 Objekt 6001h: Mess-Schritte pro Umdrehung ................80 9.3.2.2 Objekt 6002h: Gesamt Messlänge in Schritten ................. 80 9.3.3 Objekt 6003h: Presetwert ..................82 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Page 6
11.3.2 Objekt 1003h: Vordefiniertes Fehlerfeld, Bits 0 – 15 ..........97 11.4 Alarm-Meldungen ......................... 97 11.5 Sonstige Störungen ......................98 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 6 of 196 TR - ECE - BA - DGB - 0147 - 02...
Erstausgabe 22.05.2019 Zweitschnittstelle SSI erweitert 31.10.2019 Zweitschnittstelle Inkremental erweitert 06.03.2020 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 7 of 196...
V2.2.5, Layer Setting Services (LSS) und Protokolle, November 2010 CiA DS-406 V3.2, CANopen Profil für Encoder, Dezember 2006 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Service Data Object. Punkt zu Punkt Kommunikation mit Zugriff auf die Objekt-Datenliste eines Gerätes. Synchron-Serielles-Interface TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 10 of 196 TR - ECE - BA - DGB - 0147 - 02...
"CANopen Device Profile für Encoder CiA DS-406 V2.0A". Die technischen Richtlinien zum Aufbau des CANopen Netzwerks der CAN- Nutzerorganisation CiA sind für einen sicheren Betrieb zwingend einzuhalten. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Funktionsumfang der dazugehörigen EDS-Datei Firmware-Nr. Vereinbarung zwischen TR-Electronic und dem Kunden TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 12 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Geräteprofile entwickelt, in der mit der Struktur des Objektverzeichnisses und den allgemeinen Kodierungsregeln der gemeinsame Nenner aller Geräteprofile definiert ist. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Network Management Object (NMO) z.B. Life / Node-Guarding Boot-Up,… Error Control Protokoll TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 14 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Bestätigung bestätigende Dienste Abbildung 3: Gegenüberstellung von PDO/SDO-Eigenschaften TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 15 of 196...
SYNC 0001bin 1005 181h – 1FFh PDO1 (tx) 0011bin 1800h TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 16 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Im Fall eines Fehlers (SDO Response CCD = 0x80) enthält der Datenbereich einen 4-Byte-Fehlercode, der über die Fehlerursache Auskunft gibt. Die Bedeutung der Fehlercodes ist aus der Tabelle 10, Seite 95 zu entnehmen. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Page 18
0x01 SDO Response Die Bytes 1 bis 7 beinhalten die angeforderten Daten. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 18 of 196 TR - ECE - BA - DGB - 0147 - 02...
Wenn nur 1 Datenbyte (Daten 0) Daten enthält, ist der Wert von Byte 0 = "4Fh". Ist Byte 0 = 80h, wird die Übertragung abgebrochen. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
High Byte Ist Byte 0 = 80h, wird die Übertragung abgebrochen. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 20 of 196 TR - ECE - BA - DGB - 0147 - 02...
(9),(10),(11) Reset_Node --> Reset Knoten (12),(13),(14) Reset_Communication --> Reset Kommunikation TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 21 of 196...
(14) erster Zustand nach dem Einschalten. Tabelle 4: NMT-Dienste zur Gerätekontrolle TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 22 of 196 TR - ECE - BA - DGB - 0147 - 02...
Ist die Life Time = 0, ist das Life Guarding abgeschaltet. Tabelle 5: Parameter für NMT-Dienste TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
LSS identify non-configured slave Rückmeldung der LSS-Slaves auf das vorherige Kommando TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 24 of 196 TR - ECE - BA - DGB - 0147 - 02...
Byte 7 Tabelle 7: LSS-Nachricht Byte 0 enthält die Command-Specifier (CS), danach folgen 7 Byte für die Daten. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 26 of 196 TR - ECE - BA - DGB - 0147 - 02...
0x43 LSS-Slave --> LSS-Master COB-ID Reserved by CiA 0x7E4 0x44 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 27 of 196...
SDO geändert werden. Siehe hierzu auch Kap. 5.4 „Einstellen der Node-ID und Baudrate“ auf Seite 39 und Kap. 9.2.9 „Objekt 2110h: LSS Node-ID“ auf Seite 70. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany...
SDO geändert werden. Siehe hierzu auch Kap. 5.4 „Einstellen der Node-ID und Baudrate“ auf Seite 39 und Kap. 9.2.10 „Objekt 2111h: LSS-BitTiming“ auf Seite 70. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Specific Error Wenn Error Code = 255 --> applikationsspezifischer Fehler aufgetreten, sonst reserviert durch die CiA TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 30 of 196 TR - ECE - BA - DGB - 0147 - 02...
LSS-Slave --> LSS-Master Product-Code (≙Index 1018h:02) COB-ID Reserved by CiA 0x7E4 0x5B TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 31 of 196...
LSS-Slave --> LSS-Master Serial-No. (≙Index 1018h:04) COB-ID Reserved by CiA 0x7E5 0x5D TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 32 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Node-ID zurückgemeldet. Erst nach Ausführung des NMT-Dienstes Reset Communication (0x82) wird die aktuelle Node-ID zurückgemeldet. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
LSS-Adress-Attributen entsprechen, antworten mit diesem Protokoll. LSS-Slave --> LSS-Master COB-ID Reserved by CiA 0x7E4 0x4F TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 34 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Protokoll. LSS-Slave --> LSS-Master COB-ID Reserved by CiA 0x7E4 0x50 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 35 of 196...
DE-91058 Erlangen Tel. +49-9131-69086-0 Fax +49-9131-69086-79 Website: www.can-cia.org E-Mail: headquarters@can-cia.org TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 36 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Normen und Richtlinien zu beachten! Insbesondere sind die EMV-Richtlinie sowie die Schirmungs- und Erdungsrichtlinien in den jeweils gültigen Fassungen zu beachten! TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Daten-Objekte möglich. Es ist aber möglich, PDOs unter Nutzung von SDOs zu konfigurieren. Ist das Mess-System in den Zustand OPERATIONAL überführt worden, ist auch eine Übertragung von PDOs möglich. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 38 of 196...
Mode = 0 in den Zustand Waiting state bringen. NMT-Dienst Reset Communication (0x82) aufrufen, damit die neue Node-ID aktiv wird. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
2111h: LSS-BitTiming“ eingestellt. Siehe Kap.: 9.2.9 und 9.2.10. Die über SDOs eingestellte Node-ID und Baudrate entsprechen den über LSS- Dienste eingestellten Werten und überschreiben sich gegenseitig. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 40 of 196...
Die Steckerbelegungsnummer ist auf dem Typenschild des Mess-Systems vermerkt. Entsprechende Maßnahmen im Fehlerfall siehe Kapitel „Optische Anzeigen“, Seite 94. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Istwert kann nur über einen Remote-Frame übertragen werden Istwert wird asynchron mit dem Timerwert aus den Objekten 1800h und 1801h übertragen (Subindex 5) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 42 of 196...
Subindex und der Länge in Bit: Index Subindex Länge in Bit TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 43 of 196...
Seite 69. In der Standardeinstellung kann jetzt der Positionswert auf verschiedene Arten übertragen werden: TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 44 of 196 TR - ECE - BA - DGB - 0147 - 02...
7. gemapptes Objekt 0000 0000h 8. gemapptes Objekt 0000 0000h TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 45 of 196...
1F80 NMT Autostart Unsigned32 Tabelle 8: Kommunikationsspezifische Standard-Objekte segmentiertes Lesen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 46 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Im Moment des Auftretens wird ein Fehler durch eine EMCY- Nachricht signalisiert. Unsigned8 Bedeutung generischer Fehler Kommunikationsfehler (Überlauf, Fehlerstatus) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 47 of 196...
Byte 1 Byte 2 Byte 3 Fehlercode Zusatz-Fehlerinformation, wird nicht unterstützt TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 48 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
8.8 Objekt 100Ah: Hersteller Softwareversion Enthält die Firmware-Nr. (visible string) Übertragung per „Segment Protokoll“. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Node-Guarding-Protokoll. Standardwert = 0. Unsigned8 Life-Time-Faktor Byte 0 bis 2 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 50 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
0606 0000 h. Wurde eine falsche Signatur geschrieben, verweigert das Gerät die Speicherung und antwortet mit Abbruch der Übertragung: Fehlercode 0800 0020 h. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Übertragung: Fehlercode 0606 0000 h. Wurde eine falsche Signatur geschrieben, verweigert das Gerät die Wiederherstellung und antwortet mit Abbruch der Übertragung: Fehlercode 0800 0020 h. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 52 of 196...
Heartbeat time [ms], Default = 0 Die Heartbeat time ist als Vielfaches von 1 ms anzugeben. Der Eintrag für die Node- ID entspricht der Node-ID des zu überwachenden Knotens. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Revisions-Nr. Subindex4: Bei Lesezugriff liefert das Gerät Informationen über die Serien-Nr.: aktuelle Serien-Nr. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 54 of 196 TR - ECE - BA - DGB - 0147 - 02...
(nur wenn sich das Gerät im OPERATIONAL-Mode befindet) keine Änderung des NMT-Status NMT in STOPPED-Mode versetzen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
SDO Abort-Nachricht ausgegeben. Die Abort-Nachricht 0609 0030h zeigt an, dass die Aktion nicht unterstützt wird. Die Abort-Nachricht 0800 0022h zeigt an, dass die Aktion im Moment nicht ausgeführt werden kann. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 56 of 196...
2…7 Nicht unterstützt 8…15 Reserviert (immer 0) 16…31 Nicht unterstützt TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 57 of 196...
Start Der Versuch ein Bit zu ändern das nicht im Mess-System vorhanden ist, veranlasst eine Abort-Nachricht (0609 0030h). TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 58 of 196 TR - ECE - BA - DGB - 0147 - 02...
2710 TR-Produktion Unsigned8 2720 TR-Produktion Unsigned8 2721 TR-Produktion Unsigned16 … TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 59 of 196...
Page 60
EEPROM abgespeichert. Ist sofort nach Aufruf wirksam und wird dauerhaft im EEPROM abgespeichert. Segmentiertes Lesen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 60 of 196 TR - ECE - BA - DGB - 0147 - 02...
0x6002, Gesamtmesslänge in Schritten 0x2003, Anzahl Umdrehungen - Zähler 0x2004, Anzahl Umdrehungen - Nenner TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Sicherstellen, dass sich Positionierungen im stromlosen Zustand bei einem Multi-Turn Mess-System innerhalb von 512 Umdrehungen befinden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 62 of 196 TR - ECE - BA - DGB - 0147 - 02...
Gesamtmesslänge in Schritten = Anzahl Schritte pro Umdrehung * Anzahl Umdrehungen Zur Berechnung können die Parameter Schritte/Umdr. und Anzahl Umdrehungen vom Typenschild des Mess-Systems abgelesen werden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Anzahl der Umdrehungen: Anzahl Umdrehungen Zähler Anzahl der Umdrehungen = Anzahl Umdrehungen Nenner TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 64 of 196 TR - ECE - BA - DGB - 0147 - 02...
Page 65
Mess-System bei einer geringfügigen Überschreitung des Verfahrweges keinen Istwertsprung (Nullübergang) erzeugt. Der Einfachheit halber kann auch der volle Umdrehungsbereich des Mess-Systems programmiert werden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Page 66
= 1348,073499 Schritte / Umdr. * 1 Umdrehung Nenner = 5521709 Schritte (abgerundet) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 66 of 196 TR - ECE - BA - DGB - 0147 - 02...
9.2.4 Objekt 2006h: Zusätzliche Parameter/Kommandos (gerätespezifisch) Über dieses Objekt können gerätespezifische Parameter/Kommandos ausgetauscht werden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
* 0,05 s 32768 Schritte (Schritte/Integrationszeit) * Faktor = 32768 Schritte / 50 ms TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 68 of 196 TR - ECE - BA - DGB - 0147 - 02...
TPDO2 Senden bei Node-Start AUS (standard) 2 - 7 reserviert TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 69 of 196...
0x08 = 10 kbit/s 9.2.11 Objekt 2200h: DMF abspeichern Dieses Objekt dient zu Servicezwecken. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 70 of 196 TR - ECE - BA - DGB - 0147 - 02...
PDO Mapping Untergrenze 4 µs (0x0004) Obergrenze 999 µs (0x03E7) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 72 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Untergrenze programmierte Messlänge in Schritten – 1 Obergrenze Default TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 73 of 196...
0x00 = K1 zu K2 90° voreilend * 0x01 = K1 zu K2 90° nacheilend * * Drehrichtung der Mess-System-Welle im Uhrzeigersinn mit Sicht auf den Flansch. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 74 of 196...
Ausgangstreiber: RS422-Ausgangsstufe 0x01 = HTL, US Versorgungsspannung Ausgangstreiber: Gegentakt-Ausgangsstufe Versorgungsspannung muss > 8 VDC betragen. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
0 = K0 wird auf die aktuelle Position gesetzt programmierte Anzahl Impulse (Kap.: 9.2.14.2) Obergrenze TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 76 of 196 TR - ECE - BA - DGB - 0147 - 02...
Display Control Beschreibung Datentyp UNSIGNED8 Objektcode VARIABLE Zugriff PDO Mapping nein TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 77 of 196...
PDO Mapping 9.2.16 TR-Produktion Die Objekte „TR-Produktion“ sind für herstellerspezifische Funktionen reserviert. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 78 of 196 TR - ECE - BA - DGB - 0147 - 02...
Sicherstellen, dass sich Positionierungen im stromlosen Zustand bei einem Multi-Turn Mess-System innerhalb von 512 Umdrehungen befinden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Da der Wert "0" bereits als Schritt gezählt wird, ist der Endwert = Messlänge in Schritten – 1. Gesamtmesslänge in Schritten = Mess-Schritte pro Umdrehung * Anzahl der Umdrehungen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 80 of 196...
Page 81
Gesamtschrittzahl unterschritten wird und das Mess-System vor Erreichen des maximalen mechanischen Verfahrweges einen Nullübergang generiert. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Byte 3 bis 2 bis 2 bis 2 bis 2 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 82 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Timers sich auch im Cyclic Timer auswirkt und umgekehrt. Die Kommunikationsparameter 1801h benutzt ausschließlich seinen eigenen Timer, Zugriff über Subindex 5. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
2 bis 2 bis 2 Standardwert: abhängig von der Kapazität, siehe Typenschild TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 85 of 196...
59392 = E800h Umdrehungen. Da dieses Objekt nur einen 16 Bit-Wert speichern kann, wird der höherwertige Anteil der Zahl 3E800h (256.000) nicht dargestellt. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 86 of 196...
EE-PROM-Fehler Das Mess-System hat eine falsche Checksumme im EEPROM-Bereich erkannt, oder ein Schreibvorgang in das EEPROM konnte nicht erfolgreich abgeschlossen werden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
EE-PROM-Fehler Nein Reserviert für weitere Verwendung herstellerspezifische Funktionen herstellerspezifische Funktionen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 88 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Die Grenzwerte können dem gerätespezifischen Datenblatt entnommen werden. Alle Warnungen werden automatisch gelöscht, sobald sich die Betriebsparameter wieder im Normalbereich befinden. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Reserviert für weitere Verwendung Temperaturwarnung Nein herstellerspezifische Funktionen herstellerspezifische Funktionen herstellerspezifische Funktionen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 90 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Operating time Datentyp UNSIGNED32 Objektcode VARIABLE Zugriff PDO Mapping nein TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 91 of 196...
Serial number Datentyp UNSIGNED32 Objektcode VARIABLE Zugriff nein PDO Mapping TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 92 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Wenn der Fehler nicht mehr vorhanden ist, überträgt das Mess-System eine Emergency-Meldung mit dem Fehlercode "0" (Reset Fehler / kein Fehler) und Fehler- Register "0". TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
PRE-OPERATIONAL- oder den STOPPED-Mode überführt werden soll, siehe Seite 55. In diesem Fall ist die abgesetzte Emergency-Meldung auszuwerten, siehe Emergency-Fehlercodes ab Seite 96. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 94 of 196...
Keine Daten verfügbar bei Lesezugriff auf Objekt 1003h Subindex 01, siehe Seite 48. Tabelle 10: SDO-Fehlercodes TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Fehlers wird das Fehlerregister zurückgesetzt und eine EMCY-Nachricht mit Fehlercode „0x000“ übertragen. Bedeutung generischer Fehler Kommunikationsfehler (Überlauf, Fehlerstatus) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 96 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Speicherbereich im internen System getauscht werden. EE-PROM-Fehler EEPROM defekt Tabelle 12: Alarm-Meldungen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 97 of 196...
Mess-System getauscht werden. Defekt der Abtastung. Tabelle 13: Sonstige Störungen TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 98 of 196 TR - ECE - BA - DGB - 0147 - 02...
Page 99
User Manual _Commissioning Interface _Parameterization _Cause of faults and remedies TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 99 of 196...
Page 100
CANopen and CiA are registered community trademarks of CAN in Automation e.V. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 100 of 196 TR - ECE - BA - DGB - 0147 - 02...
Page 101
4.7.7.3 LSS identify non-configured remote slave protocol ..............133 4.7.7.4 LSS identify non-configured slave protocol ................133 4.8 Device profile .......................... 134 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Page 102
8.17 Object 1021h: Store EDS ..................... 153 8.18 Object 1022h: Store format ....................153 8.19 Object 1029h: Error behavior object ..................153 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 102 of 196...
Page 103
9.3.2.1 Object 6001h: Measuring units per revolution ................178 9.3.2.2 Object 6002h: Total measuring range in measuring units............178 9.3.3 Object 6003h: Preset value..................180 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Page 104
11.3.2 Object 1003h: Pre-defined Error field, bits 0 – 15 ..........195 11.4 Alarm messages ........................195 11.5 Other faults ........................... 196 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 104 of 196...
Additional SSI interface added 10/31/2019 Additional incremental interface added 03/06/2020 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 105 of 196...
- Series 582: www.tr-electronic.de/s/S020796 - Series 802: www.tr-electronic.de/s/S020797 - Series 1102: www.tr-electronic.de/s/S020798 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 106 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
V2.2.5, Layer Setting Services (LSS) and Protocols, November 2010 CiA DS-406 V3.2, CANopen Profile for Encoder, December 2006 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Service Data Object. Peer to peer communication with access to the Object Dictionary of a device. Synchronous-Serial-Interface TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 108 of 196 TR - ECE - BA - DGB - 0147 - 02...
The technical guidelines for the structure of the CANopen network from the CAN User Organization CiA are always to be observed in order to ensure safe operation. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany...
Firmware no. Declaration between TR electronic and the customer TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 110 of 196 TR - ECE - BA - DGB - 0147 - 02...
Network Management Object (NMO) e.g. Life / Node-Guarding Boot-Up,… Error Control Protocol TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 112 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
CAN pure acknowledged services no Acknowledgement Figure 3: Comparison of PDO/SDO characteristics TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 113 of 196...
SYNC 0001bin 1005 181h – 1FFh PDO1 (tx) 0011bin 1800h TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 114 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
In the case of an error (SDO response CCD = 0x80) the data field contains a 4-byte error code, which gives information about the error cause. Meaning of the error codes, see Table 10 on page 193. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Page 116
0x01 SDO Response The bytes 1 to 7 contain the requested data. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 116 of 196 TR - ECE - BA - DGB - 0147 - 02...
If only 1 data byte (Data 0) contains data the value of byte 0 is "4FH". If byte 0 = 80h the transfer has been aborted. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany...
High Byte If byte 0 = 80h the transfer has been aborted. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 118 of 196 TR - ECE - BA - DGB - 0147 - 02...
(4),(7) Enter_PRE-OPERATIONAL_State --> Pre-Operational (5),(8) Stop_Remote_Node (9),(10),(11) Reset_Node (12),(13),(14) Reset_Communication TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 119 of 196...
Afterwards transition into the INITIALIZATION state, first state (14) after Power on. Table 4: NMT device control services TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 120 of 196 TR - ECE - BA - DGB - 0147 - 02...
Guard Time = 0: No monitoring active Life Time = 0: Life guarding disabled Table 5: Parameter for NMT services TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
● LSS identify non-configured remote slave ● LSS identify non-configured slave TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 122 of 196 TR - ECE - BA - DGB - 0147 - 02...
Byte 7 Table 7: LSS message Byte 0 contains the Command-Specifier (CS), afterwards 7 byte data are following. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 124 of 196 TR - ECE - BA - DGB - 0147 - 02...
0x43 LSS-Slave --> LSS-Master COB-ID Reserved by CiA 0x7E4 0x44 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 125 of 196...
SDO. See also chapter 5.4 "Setting the Node-ID and Baud rate" on page 137 and chap. 9.2.9 "Object 2110h: LSS Node-ID" on page 168. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 126 of 196...
BitTiming" using SDO. See also chapter 5.4 "Setting the Node-ID and Baud rate" on page 137 and chap. 9.2.10 "Object 2111h: LSS BitTiming" on page 168. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany...
Specific Error if Error Code = 255 --> application specific error occurred, otherwise reserved by CiA TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 128 of 196 TR - ECE - BA - DGB - 0147 - 02...
LSS-Slave --> LSS-Master Product-Code (≙Index 1018h:02) COB-ID Reserved by CiA 0x7E4 0x5B TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 129 of 196...
LSS-Slave --> LSS-Master Serial-No. (≙Index 1018h:04) COB-ID Reserved by CiA 0x7E5 0x5D TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 130 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Configure Node-ID service, the original Node-ID is reported. Only after execution of the NMT service Reset Communication (0x82) the actual Node-ID is reported. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
LSS-Slave --> LSS-Master Reserved by CiA COB-ID 0x7E4 0x4F TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 132 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
LSS-Slave --> LSS-Master COB-ID Reserved by CiA 0x7E4 0x50 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 133 of 196...
DE-91058 Erlangen Tel. +49-9131-69086-0 Fax +49-9131-69086-79 Website: www.can-cia.org e-mail: headquarters@can-cia.org TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 134 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
In particular, the applicable EMC directive and the shielding and grounding guidelines must be observed! TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Objects is possible. But it is possible to configure PDOs with the help of SDOs. If the measuring system was transferred into the OPERATIONAL state, also a transmission of PDOs is possible. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 136 of 196...
Mode = 0, to switch the LSS slave into Waiting state. Perform NMT service Reset Communication (0x82), to switch the new Node-ID active. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
2111h: LSS BitTiming". See chapters 9.2.9 and 9.2.10. The Node-ID and Baud rate set via SDOs correspond to the values set via LSS services and overwrite each other. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 138 of 196...
Corresponding measures in case of an error see chapter “Optical displays”, page 192. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Actual value can be transferred only over a remote frame Actual value is transferred asynchronously with the timer value from object 1800h and 1801h (sub-index 5) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 140 of 196...
PDO by their index, sub-index and length in bit: Index Sub-index Length in bit TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
"Object 2101h: Send PDO at Node-Start" on page 167. In the default setting the measuring system position value can be transmitted in different ways: TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 142 of 196...
7. mapped object 0000 0000h 8. mapped object 0000 0000h TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 143 of 196...
NMT startup Unsigned32 Table 8: Communication specific standard objects segmented reading TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 144 of 196 TR - ECE - BA - DGB - 0147 - 02...
EMCY message. Unsigned8 Meaning generic error communication error (overrun, error state) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 145 of 196...
Byte 2 Byte 3 Error code Additional Information, not supported TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 146 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
8.8 Object 100Ah: Software version Contains the manufacturer software version (visible string), transmission via “Segment Protocol”. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Default value = 0. Unsigned8 Life Time Factor Byte 0 to 2 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 148 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Error code 0606 0000h. If a wrong signature is written, the device refuses to save and responds with abort domain transfer: Error code 0800 0020h. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
If a wrong signature is written, the device refuses to restore the defaults and responds with abort domain transfer: Error code 0800 0020h. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 150 of 196...
The heartbeat time is given in multiples of 1 ms. The entry for the Node-ID corresponds to the Node-ID of the node to be guarded. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Sub-index3: Provides information about the Revision-No.: current Revision-No. Sub-index4: Provides information about the Serial-No.: current Serial-No. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 152 of 196 TR - ECE - BA - DGB - 0147 - 02...
(only if currently in NMT state OPERATIONAL) No change of the NMT state Change to NMT state STOPPED TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
The SDO abort code 0800 0022h shall indicate that a requested action can currently not be performed. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 154 of 196...
2..7 Not supported 8…15 Reserved (always 0) 16…31 Not supported TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 155 of 196...
An attempt to change a bit of a functionality that is not supported by the CANopen device shall be responded with the abort message 0609 0030h. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany...
2710 TR-Production Unsigned8 2720 TR-Production Unsigned8 2721 TR-Production Unsigned16 … TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 157 of 196...
Page 158
"1010, Store parameters". Is immediately active and durably stored in the EEPROM after a write command. segmented reading TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 158 of 196 TR - ECE - BA - DGB - 0147 - 02...
0x2002, Total measuring range in steps 0x6002, Total measuring range in steps 0x2003, Number of revolution - numerator 0x2004, Number of revolution - denominator TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
2 Ensure that every positioning in the de-energized state for a multi-turn measuring system is within 512 revolutions. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 160 of 196...
Total measuring range = Steps per revolution * Number of revolutions To calculate, the parameters steps/rev. and the number of revolutions can be read on the measuring system nameplate. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Number of revolutions numerator Number of revolutions = Number of revolutions denominator TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 162 of 196 TR - ECE - BA - DGB - 0147 - 02...
Page 163
(zero transition) if the distance travelled is exceeded. To simplify matters the complete revolution range of the measuring system can also be programmed. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Page 164
= 1348.073499 steps / rev. * 1 revolution denominator = 5521709 steps (rounded off) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 164 of 196 TR - ECE - BA - DGB - 0147 - 02...
See Object 2000h: Mode selection TR / CiA DS-406. 9.2.4 Object 2006h: Additional Parameter/Commands (device specific) About this object device specific parameters and commands can be exchanged. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
* 0.05 s = 32768 steps (Steps/integration time) * factor = 32768 steps / 50 ms TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 166 of 196 TR - ECE - BA - DGB - 0147 - 02...
Send TPDO2 at Node-Start off (default) 2 - 7 Reserved for further use TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 167 of 196...
0x08 = 10 kbit/s 9.2.11 Object 2200h: Store DMF This object is for service purposes. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 168 of 196 TR - ECE - BA - DGB - 0147 - 02...
Value 0x00 = Gray 0x01 = Binary 0x02 = Gray cut TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 169 of 196...
Lower limit 4 µs (0x0004) Upper limit 999 µs (0x03E7) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 170 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
Lower limit programmed measuring length in steps – 1 Upper limit Default TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 171 of 196...
0x00 = K1 leads to K2 by 90° * 0x01 = K1 lagging to K2 by 90° * * Turning direction clockwise with view on the flange. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 172 of 196...
0x00 = TTL, 5 VDC; Output driver: RS422 0x01 = HTL, US Supply voltage; Output driver: Push-Pull The supply voltage must be > 8 VDC TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
0 = K0 is set to the current position programmed number of pulses (chapter: 9.2.14.2) Upper limit TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 174 of 196 TR - ECE - BA - DGB - 0147 - 02...
Display Control Data type UNSIGNED8 Object code VARIABLE Access PDO mapping TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 175 of 196...
PDO mapping 9.2.16 TR-Production The objects "TR-Produktion" are reserved for manufacturer-specific functions. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 176 of 196 TR - ECE - BA - DGB - 0147 - 02...
Ensure that every positioning in the de-energized state for a multi-turn measuring system is within 512 revolutions. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
"0" is already counted as a step, the end value = measurement length in steps - 1. Total measuring range = Steps per revolution * Number of revolutions TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 178 of 196...
Page 179
TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Byte 3 to 2 to 2 to 2 to 2 TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 180 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
That means that a change in the event timer causes a change in the cyclic timer and vice versa. The communication parameter 1801h exclusively uses its own timer, access over sub-index 5. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
2 to 2 to 2 Standard value: depending on capacity marked on nameplate TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Standard value: 59392 = E800h revolutions. Since this object only can store a 16-bit value, the high-order word with the number 3E800h (256.000) is not represented. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 184 of 196...
EE-PROM error The measuring system detects a wrong checksum in the EEPROM area or a write process into the EEPROM could not be finished successfully. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
EE-PROM error Manufacturer specific functions Manufacturer specific functions Manufacturer specific functions TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 186 of 196 TR - ECE - BA - DGB - 0147 - 02...
Limits: The limit values can be seen on the device specific data sheet. All warnings are cleared if the tolerances are again within normal parameters. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
Temperature warning Manufacturer specific functions Manufacturer specific functions Manufacturer specific functions TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 188 of 196 TR - ECE - BA - DGB - 0147 - 02...
Operating time Data type UNSIGNED32 Object code VARIABLE Access PDO mapping TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02 Page 189 of 196...
Serial number Data type UNSIGNED32 Object code VARIABLE Access PDO mapping TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 190 of 196 TR - ECE - BA - DGB - 0147 - 02 03/06/2020...
1001h. If the error disappears, the measuring system transmits an emergency message with error code "0" (reset error / no error) and error register "0". TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020...
STOPPED-Mode, see page 153. In this case the emergency massage should be evaluated, see "Emergency Error codes" on page 194. TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 192 of 196...
No data available access on object 1003h sub-index 1, see page 146. Table 10: SDO Error codes TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
"0x000" is transferred. Meaning generic error communication error (overrun, error state) TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 194 of 196 TR - ECE - BA - DGB - 0147 - 02...
EE-PROM error EE-PROM defective Table 12: Alarm messages TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany 03/06/2020 TR - ECE - BA - DGB - 0147 - 02...
Table 13: Other faults TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany Page 196 of 196 TR - ECE - BA - DGB - 0147 - 02...