Installing The Hydraulic Unit; Installation Precautions; Positioning The Hydraulic Unit - Fujitsu Waterstage WOYA060LFCA Installation And Operating Manual

Air to water heat pump, split system
Hide thumbs Also See for Waterstage WOYA060LFCA:
Table of Contents

Advertisement

Air to Water Heat Pump, split system
2 .5

Installing the hydraulic unit

2 .5 .1 Installation precautions

• Choose the location of the appliance after discussion
with the client.
• The room in which the appliance operates must
comply with the prevailing regulations.
• To facilitate maintenance and to allow access to the
various components, we recommend that you provide
sufficient space all around the hydraulic unit.
350 mm
mini
300 mm
mini
• According
to
standard
requirements and HP environment), the room
where the HP is installed shall have a volume
higher than: Unit refrigerant load in kg / 0.44kg/m
If not, it must be ensured that:
- whether the room is mechanically ventilated,
- or room door is remain opened when the installer
works on the HP.
• Be careful not to bring inflammable gas near to the
heat pump during its installation, in particular when
it requires brazing. The appliances are not fireproof
and should therefore not be installed in a potentially
explosive atmosphere.
- To avoid condensation inside the condenser, remove
the refrigerant circuit caps only when completing the
refrigerant connections
- If the refrigerant connection only occurs at the end of
the installation, be sure that the refrigerant circuit caps*
remain in place and tight throughout the installation
duration.
* (hydraulic unit side and outdoor unit side).
- After every intervention on the refrigeration circuit and
before final connection, take care to replace the plugs
in order to avoid any pollution from the refrigeration
circuit (The sealing with tape is prohibited).
- 18 -
1000 mm
EN
378-1
(safety
3

2 .5 .2 Positioning the hydraulic unit

- Fix the support solidly (4 screws and plugs) to a flat,
hard-wearing wall (not a light partition) ensuring that it
is correctly levelled.
- Hook the appliance onto its support.
538 mm
300 mm
118 mm
mini
418 mm
mini
2
(S)
figure 15 - Mounting bracket
Installation and operation manual "1764 - EN"
350 mm
mini
mini
188 mm
(S)
1

Hide quick links:

Advertisement

Table of Contents