Technical Data - Honeywell 010690.02 Mounting And Connection Instructions

Mains/charger unit 12 v dc / 40 ah
Table of Contents

Advertisement

Available languages

Available languages

8
8. Application as per VdS
- The power supply may not be connected parallel.
- The temperature sensor for the power supply must be fixed to the battery.
- The power supply must be installed in a metal housing.
- The battery must be fixed with Velcro (

9. Technical data

Rated operating voltage
Operating voltage range
Frequency
Power consumption
Maximum constant current
Short-term continuous current drain (5 min.)
Maximum charging current
Approved accum. capacity as per VdS
No. of connectible accumulators
Possible accumulator combinations
Current consumption as per VdS for 60 hours:
at 40Ah accumulator capacity
Permanent accumulator monitoring
Temperature-guided accum. charging voltage
Operating temperature range
Storage temperature range
Environmental Class as per VdS
PCB dimensions:
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
Mounting and Connection Instructions Mains/charger unit 12 V DC / 40 Ah
Dual lock fasteners)
230 V AC
-15 % to +10 %
40 Hz to 60 Hz
100 VA
1.5 A
2.2 A max.
(
with charged accum.
1.5 A
40 Ah max.
2 max.
e.g. 2x10 / 2x16 / 1x24 / 1x38 Ah
Approx. 650 mA
-5 °C to +45 °C
-25 °C to +70 °C
II
97.5 x 250 mm
P00212-10-002-05
2013-09-16
© 2013 Novar GmbH
.
)