Chapter 4 Performance specification
In Write dialog box as above, set the position where the module to be written is mounted with slot No., and
select writing with communication option set to 'basic parameter'.
Remark
[Note1] If user defined frame has been prepared, let it set to frame in communication option to write frame
only. Similarly to this, if 'All' is selected, basic parameter and frame can be written at a time.
[Note2] Check the power status of PLC prior to writing of parameter or frame. If powered off while writing,
data in flash memory of Cnet I/F module may be crushed.
[Note3] Switch over PLC to STOP mode when writing parameter and frame. If writing while PLC running,
writing error may occur. In this case, power off and then let it on back to perform writing again
after switching over PLC to STOP mode
If writing of parameters is completed, the completion message as in the following figure is displayed.
If parameter writing is performed, Cnet operation of the correspondent channel stops. Therefore, after parameter
writing is completed, select [Online]-[Change RUN/STOP] to switch operation of the correspondent channel over
to run.
4-15