Write_Epc_Mem - Siemens SIMATIC RF600 Series Configuration Manual

Hide thumbs Also See for SIMATIC RF600 Series:
Table of Contents

Advertisement

Programming via Rockwell controller
9.5 Programming add-on instructions
9.5.2.6

Write_EPC_Mem

The "Write_EPC_Mem" block overwrites the EPC memory of the RF600 transponder. The
length of the EPC memory to be overwritten is specified by the "LEN_DATA" parameter.
Figure 9-13
Table 9- 17
Parameter
LEN_DATA
LEN_ID
EPCID_UID
IDENT_DATA
128
"Write_EPC_Mem" block
Explanation of the "Write_EPC_Mem" block
Data type
DINT
DINT
SINT[62]
SINT[10]
Default values
Description
W#16#0
Length of the EPC memory to be
overwritten (1 ... 62 bytes)
B#16#0
Length of the EPC-ID/UID
Default value: 0x00 ≙ unspecified
single tag access (RF680R, RF685R)
0
Buffer for up to 62 bytes EPC-ID, 8
bytes UID or 4 bytes handle ID.
2 - 62-byte EPC-ID is entered at
the start of the buffer (length is set
by "LEN_ID")
8-byte UID is entered at the start
of the buffer ("LEN_ID = 8")
4-byte handle ID must be entered
in the array element [5]-[8]
("LEN_ID = 8")
Default value: 0x00 ≙ unspecified
single tag access (RF620R, RF630R,
RF640R)
0
Data buffer with the EPC memory data
to be overwritten.
Note.
When necessary a byte/array of any
size can be transferred to this parame-
ter. Note that the array must be ≥ 10
bytes long (e.g. "SINT[12400]").