Lhedv series direct vent insert
Hide thumbs Also See for LHECDV30:

Advertisement

INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL
BEFORE INSTALLING AND
USING APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLO-
SION MAY RESULT CAUSING
PROPERTY DAMAGE, PER-
SONAL INJURY OR LOSS OF
LIFE.
FOR YOUR SAFETY
Installation and service must
be performed by a qualified
installer, service agency or
the gas supplier.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch;
do not use any phone in your
building.
Immediately call your gas
supplier from your neighbor's
phone. Follow the gas suppliers
instructions.
If you cannot reach your gas
supplier call the fire department.
DO NOT STORE OR USE
GASOLINE OR OTHER
FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF
THIS OR ANY OTHER
APPLIANCE.
Direct Vent Insert
Models: LHERDV20
LHERDV30
LHECDV20
LHECDV30
Homeowner's Installation and
Operating Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
C E R T I F I E D
10004894 1/07 Rev. 4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LHECDV30 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vermont Castings LHECDV30

  • Page 1 THIS OR ANY OTHER APPLIANCE. Direct Vent Insert Models: LHERDV20 LHERDV30 LHECDV20 LHECDV30 Homeowner's Installation and Operating Manual INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. C E R T I F I E D...
  • Page 2: Table Of Contents

    LHEDV Series Direct Vent Insert PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING THIS APPLIANCE. Thank you and congratulations on your purchase of a CFM Corporation fireplace insert. IMPORTANT - Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the manufacturers' warranty.
  • Page 3: Important Curing/Burning Instructions

    fireplace cavity (min. 25¹⁄₄"W x 17¹⁄₂"H x 13¹⁄₂" D (641 x 438 x 343 mm) for the LHECDV20 and LHERDV20, 28³⁄₄"W x 21"H x 15¹⁄₂"D (730 x 533 x 394 mm) for LHECDV30 and LHERDV30), the design of the chimney for effective venting should be determined.
  • Page 4: Fireplace & Trim Dimensions

    (457mm) 18" (457 mm) Gas Inlet Knockout U - Firebox depth at insert back height (V) V - Insert back height NOTE: LHESLGA is only available for Model LHEC30 and LHER30 LHECDV30 LHERDV30 26³⁄₄" (680 mm) 26³⁄₄" HEZC specs 38¹⁄₄"...
  • Page 5: Mantels

    Zero Clearance Kit and the requirements of the Air Kit. NOTE: If a Zero Clearance Kit is required for mod- els LHECDV20/LHERDV20/LHECDV30/LHERDV30 Direct Vent Inserts, only the CFM Corporation zero clearance kit HEZC combined with the HEDVCAK is approved to be used.
  • Page 6: Gas Specifications

    LHEDV Series Direct Vent Insert Gas Specifications Max. Input Model Fuel Control Btu/h LHECDV20RN Natural Millivolt 20,000 14,000 Hi/Lo LHECDV20RP Propane Millivolt 20,000 15,000 Hi/Lo LHECDV20RFN Natural Comfort 20,000 14,000 Control LHECDV20RFP Propane Comfort 20,000 15,000 Control LHERDV20RN Natural Millivolt 20,000 14,000 Hi/Lo LHERDV20RP Propane Millivolt 20,000 15,000 Hi/Lo...
  • Page 7: Gas Supply Pressures

    3/8" Nip- CAUTION: Logs may be hot! 4. For Model LHECDV20: remove burner assembly and bracket rear log. For Model LHECDV30: remove bracket rear log and cover fan. 5. Remove the fan mounting nuts (2 nuts). (Fig. 5) 6. Slip off the electrical connector at the motor.
  • Page 8: Remote Switch Wiring

    fireplace opening 25¹⁄₄"W x 17¹⁄₂" H x 13¹⁄₂"D sembly x 438 x 343 mm) 28³⁄₄"W x 21"H x 15¹⁄₂"D LHECDV30 and LHERDV30 and has been installed in accordance with the National, Provincial/State and local building codes and is constructed of noncombustible materials.
  • Page 9: Liner Installation

    Liner Installation The collar extending down from the termination base is the air intake connector. Be sure the flex vent, which is connected to this collar, is also connected to the labelled air intake flue collar on the fireplace. Make sure the flex vent is attached on the correct collar and cap for exhaust as well.
  • Page 10 LHEDV Series Direct Vent Insert Flue gas exits through the vent termination rain Outside combus- tion air enters through the lower level of the vent termination Secure with clamp and three screws A or B Vent with 7" Inside Minimum and 14"...
  • Page 11: Round Vent Termination Installation

    Round Vent Termination Installation Round Vent Termination Model HEDVRT is designed to be installed onto the LHECDV20, LHERDV20, LH- ECDV30 and LHERDV30 direct vent insert fireplaces. This round vent termination is built to be installed onto any type A-vent round chimney or B-vent round chim- ney.
  • Page 12: Venting Components

    LHEDV Series Direct Vent Insert FP1298 RHEDV vent components 2/03 FP1299 RHEDV vent components 2/03 FP1327 vent components 4/03 FP1300 Flex pipe 2/03 FP1300 Venting Components 8" x 12" Vent Termination Kit (Fit typical 8" x 12" and 9" x 13" flue tile) Kit Includes: High Temperature Sealant 12"...
  • Page 13: Operating Instructions

    2. Lift up and unhook glass frame at the top. 10004894 Operating Instructions LHECDV30 and LHERDV30 1. Unhook the frame window by pulling the handle of the two (2) latches at the bottom part of the window frame; pull the left side latch counterclockwise and the right side latch, clockwise.
  • Page 14: Large Lava Rock Placement

    Place the burner lava rock on the front area of the burner housing. (Fig. 22) LHECDV30, LHERDV30 (Fig. 23) a. Place the rear center log (KR24). Use the log's bottom holes to lo- cate it onto the two (2) pin studs of the rear log bracket on the center.
  • Page 15: Flame Characteristics

    Flame Characteristics It is important to periodically perform a visual check of the pilot and the burner flames. Compare them to the Figure 26 and Figure 27 or 28. If any of the flames ap- pear abnormal call a service person. 3/8"...
  • Page 16: Lighting & Operating Instructions

    LHEDV Series Direct Vent Insert Lighting and Operating Instructions FOR YOUR SAFETY READ BEFORE LIGHTING WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This heater has a pilot which must be lit manu- ally.
  • Page 17: Troubleshooting Gas Control (820 Millivolt Gas Valve)

    Troubleshooting the Gas Control System NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position. WARNING: Before doing any gas control service work, remove glass front. SYMPTOM 1. Spark ignitor will not light A.
  • Page 18: Troubleshooting Gas Control (Honeywell)

    LHEDV Series Direct Vent Insert Troubleshooting the Gas Control System START Gas Supply On Pilot Lights With Piezo Ignitor Pilot Stays Lit Pilot Lights Main Burner System OK. Honeywell Millivolt Valve CHECK Supply Line Hooked Up Shutoff Valve Open Lockout Has Engaged. Wait 60 Seconds And Try Again.
  • Page 19: Instructions For Rf Comfort Control Valve

    Instructions for RF Comfort Control Valve The Comfort Control Valve allows remote control of temperature, fan and flame appearance. NOTE: The antenna should hang in free air away from grounded metal. Operation 1. If the manual switch is in remote position, switch it to LOCAL.
  • Page 20: Auto Mode

    LHEDV Series Direct Vent Insert Delay Timer Mode The shut off delay timer has a maximum of 2 hours and a minimum of zero minutes. To change the timer level, press the time key followed by an arrow key. Pushing the key once will change the timer by 10 minutes.
  • Page 21 2. Slide the Remote/Local switch to REMOTE and teach the valve a transmitter (refer to Item 6, page 1). The Error Code will clear itself after approximate- ly 1¹⁄₂ minutes and return to normal operation. LED Count Service Action Replace valve Confirm stepper motor connection exists Confirm fan connection exists and...
  • Page 22 LHEDV Series Direct Vent Insert Comfort Valve system control sequence of operation with transmitter Local Path If manual switch is set to LOCAL, did main burner light? Transmitter con- trols fan Turn pilotstat knob to PILOT to turn off main burner Turn pilotstat knob to OFF to turn valve completely...
  • Page 23: Maintenance

    Burner and Burner Compartment It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out. Remove and replace the logs as per the instructions in this manual.
  • Page 24: Replacement Parts

    LHEDV Series Direct Vent Insert LHERDV20/LHECDV20 LHERDV30/LHECDV30 22a/b • CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. LHEDV Series 6a/b 7a/b ��� 24a/b 23 a/b...
  • Page 25 51865 54103 51704 51738 51882 10005297 10005066 57317 57317 10005295 10005067 LHEDV Series Direct Vent Insert LHERDV30 LHECDV30 10004866 10004866 10004874 (KR22) 10004874 (KR22) 10004875 (KR23) 10004875 (KR23) 10004876 (KR24) 10004876 (KR24) 10004878 (KR25) 10004878 (KR25) 10004879 (KR26) 10004879 (KR26)
  • Page 26 LHEDV Series Direct Vent Insert LHE Series (continued) Ref. Description Remote Switch (for RN or RP Units) Remote Wire Harness w/Terminals (for RN or RP Units) Ceramic Fiber Brick FP (Optional) Gasket Fan Cover Flexible Connector (6") Bracket Rear Log Assembly Bracket Log Support Assembly Gasket Cover Gas Line Access Bracket Support Grate...
  • Page 27: Optional Accessories

    Remote Controls Optional remote control units are available to control different functions of the appliance. Model Function(s) Controlled ON/OFF ON/OFF and Temperature IMTFK Wall mounted thermostat control NOTE: These remote controls are for RN/RP units only. Zero Clearance Kit For installations other than in existing woodburning fire- places such as new construction or renovation projects, a Zero Clearance Kit must be used.
  • Page 28 LHEDV Series Direct Vent Insert 10004894...
  • Page 29 LHEDV Series Direct Vent Insert 10004894...
  • Page 30 LHEDV Series Direct Vent Insert 10004894...
  • Page 31: Warranty

    PRODUCT COVERED BY THIS WARRANTY All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic gas fireplaces equipped with an Insta- Flame Ceramic Burner, or standard steel tube burner. BASIC WARRANTY CFM Corporation (hereinafter referred to collectively as the Company) warrants that your new Vermont Castings or Majestic Gas Fireplace/ Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions...
  • Page 32: Efficiency Ratings

    Model EnerGuide Ratings Fireplace Efficiency (%) LHECDV20RN 61.3 LHECDV20RP 61.3 LHECDV20RFN 61.3 LHECDV30RFP 61.3 LHERDV20RN 59.7 LHERDV20RP 59.7 LHECDV30RN 61.5 LHECDV30RP 61.5 LHECDV30RFN 61.5 LHECDV30RFP 61.5 LHERDV30RN 64.1 LHERDV30RP 64.1 410 Admiral Blvd. • Mississauga, Ontario, Canada L5T 2N6 800-668-5323 • www.cfmcorp.com Efficiency Ratings Steady State (%) Fan-OFF...