AMC2 enclosure with 1
DIN rail
Connecting the main AC supply X
1.
2.
3.
4.
Connecting the cover grounding cable
1.
2.
Refer to
3.3
Connections for supporting Universal
Power Supply
Precondition: Before switching to battery operation, disconnect
the AC power cable.
Notice!
Use 12 V 7 (7,2) Ah lead batteries only.
Notice!
Change the lead batteries every 5 years.
Bosch Security Systems B.V.
Connect the ground cable to the main grounding point
(Figure 1.1, position 8).
Connect the neutral wire to terminal N (Figure 3.2).
Connect the phase wire to terminal L1 (Figure 3.2).
Shorten the external supply wires so that the ground wire
is a minimum of 20 mm longer than the live wires.
This will prevent the ground wire from being
accidentally disconnected.
Connect the mounted grounding cable (see position F of
Parts included, page 6 ) to the cover grounding point
(Figure 1.1, position 1) and to the grounding point on the
cover of the enclosure.
Make sure that the screws of the two earthing points are
sufficiently tightened.
Parts included, page 6
Cable assembly, page 21
Connections | en
2020-07 | V04 | F.01U.330.018