v Design the flow loop to minimize the total pressure drop within the flow loop. The
Optional Low Impedance Quick Connect feature (shown in Figure 5 on page 16
through Figure 8 on page 19) cannot be the Parker quick-connect couplings that
are used on the heat exchanger because of the excessive pressure drop
associated with flowing through four quick-connect pairs in series. These must be
very low, near 0, flow impedance quick connects. Alternatively, these quick
connects can be eliminated and replaced with a hose barb connection.
15
Chapter 2. Heat exchanger planning, specifications, and requirements