11.4.6 Diagnosing the Boiler System
To run a series of test procedures for a system diagnosis, press the
Back button (
) and the Menu button (
seconds, and then select "6. Test Mode".
Rotate the Command dial (
procedures. Press the Command dial (
Press the Back button (
) to return to the previous screen or
menu.
Item
Test the fan operation by manually
changing the fan speed.
From a stopped state, the fan speed
gradually increases and reaches
1. Fan Motor
the top speed, and then the fan
speed decreases until the fan stops
operating.
Rotate the Command dial (
or stop the fan test.
Test the boiler pump operation.
The boiler pump is turned on as soon
as you enter the test mode.
2. Boiler Pump
Press the Command dial (
toggle the pump operation (On ->
Off / Off -> On).
Test the Zone 1 pump operation.
The Zone 1 pump is turned on as
soon as you enter the test mode.
3. Zone 1 Pump
Press the Command dial (
toggle the pump operation (On ->
Off / Off -> On).
) simultaneously for 3
) to switch between the test
) to run a test procedure.
Description
) to run
) to
) to
Item
Test the zone 2 pump operation.
The zone 2 pump is turned on as
soon as you enter the test mode.
Press the Command dial (
4. Zone 2 Pump
toggle the pump operation (On ->
Off / Off -> On).
This option is available only when
the "Zone Pump System" is active.
Test the Zone 3 pump operation.
The Zone 3 pump is turned on as
soon as you enter the test mode.
5. Zone 3 Pump
Press the Command dial (
toggle the pump operation (On ->
Off / Off -> On).
Test the 3 Way valve operation.
The 3 Way valve is turned on as soon
as you enter the test mode.
6. 3 Way Valve Output
Press the Command dial (
toggle the valve operation (On -> Off
/ Off -> On).
Test the Flow control valve operation.
Rotate the valve from its current
position to fully open (0%), then fully
closed (100%) and then back to the
7. Flow Control Valve
starting position while checking
Output
feedback.
Display of the valve close ratio %
Display of "FEEDBACK" when
detecting the feedback
Test the Mixing valve operation. Rotate
the valve from its current position
to fully open (0%), then fully closed
(100%) and then back to the starting
8. Mixing Valve
position while checking feedback.
Output
Display of the valve close ratio %
Display of "FEEDBACK" when
detecting the feedback
Test the dual venturi operation.
The dual venturi is turned on as soon
as you enter the test mode.
9. Dual Venturi
Press the Command dial (
toggle the dual venturi operation (On
-> Off / Off -> On).
Test the recirculation pump.
The recirculation pump is turned on
as soon as you enter the test mode.
10. Recirc. Pump
Press the Command dial (
toggle the recirculation pump (On ->
Off / Off -> On).
Description
) to
) to
) to
) to
) to
Operating the Boiler
99