Installing and connecting the device

3.2 Mounting the device

Clearances
Ensure that the following clearances measurements to another component or to a wall of a
housing are complied with:
● Below the device: ≥ 50 mm
● Above the device: ≥ 50 mm
3.2
Mounting the device
3.2.1

Mounting instructions

Note the following:
● The device is approved for indoor operation only.
● For installation in a cabinet, observe the SIMATIC setup guidelines
(http://support.automation.siemens.com/WW/view/de/1064706) as well as the relevant
DIN/VDE requirements or the applicable country-specific regulations.
● When the device is used in the area of Industrial Control Equipment in accordance with
UL61010-2-201, note that the device is classified as "Open equipment".
● Install all the expansions in the device before mounting the device on a DIN rail or a wall,
see section "Expand device (Page 29)".
● Siemens recommends you use 0.6 Nm tightening torque to install the mounting clamps
and brackets.