Page 3
1 Calibration Instruction for Salwico ST400 O2 1 Calibration Instruction for Salwico ST400 1.1 Preliminaries This instructions applies to the following products: Figure 1. Salwico ST400 O2 0-25%. Part no. 4461 The O sensor is Electrochemical and measures O content by means of chemical reaction.
Page 4
1 Calibration Instruction for Salwico ST400 O2 Calibration Instruction Test points SPAN potentiometer ZERO potentiometer 1.2 Prerequisites Use the arrow keys on the control panel to manoeuvre through the different menus. Press the right arrow key to access the menu tree.
Page 5
O content is zero per cent. We recommend the Consilium article no. 5201006-00A with 100% N Connect a Multi-meter (set to mA) to the test points. Connect the gas bottle and open the regulator valve.
Page 6
1 Calibration Instruction for Salwico ST400 O2 Calibration Instruction 1.5 Reconnecting disabled detectors All disablements in the Salwico GS5000 gas detection system are presented in the disablements list. Any enablement is made from this list. Scroll to Menu » Disablements. Choose the detector you just disabled and press Options.