Summary of Contents for Trane Jupiter JDAC Series
Page 1
Installation Installazione Operation Funzionamento Maintenance Manutenzione Unità ad alta precisione Jupiter Jupiter Close Control Units Unità a espansione diretta Direct expansion units JDAC / JUAC / JDAV / JUAV / JDWC / JUWC / JDWV / JUWV JDAC / JUAC / JDAV / JUAV / JDWC / JUWC / JDWV / JUWV Taglie: 0115 –...
Page 2
VerSion: 1.0 DAte: MARCH 2010 trAne PoLiCY iS one oF ContinUoUS teCHnoLGiCAL innoVAtion AnD tHe CoMPAnY tHereFore reSerVeS tHe riGHt to AMenD AnY DAtA Herein WitHoUt Prior notiCe.
Contents GenerAL inStrUCtionS Checks every six months information contained in the manual Annual checks Symbols Checks to be performed every sixty months Storage Cleaning and replacing the filters Storage after use troubleshooting Disposal CHiLLeD WAter Unit – CentriFUGAL FAnS Tagl Disposal of the machine technical characteristics SAFetY...
GENERAL INSTRUCTIONS Disposal of the machine the following instructions deal with the disposal of trAne Information contained in the manual machines. the procedures described below are guidelines the present manual describes the Jupiter conditioning only, provided to make the machine disassembling easier.
Page 5
• AIR FILTERS • COMPRESSORS AND LIQUID SEPARATORS Remove the air filters. WARNING! Pay attention to oil contained in - Materials: metallic net, synthetic fibre. the compressors. Avoid any loss of oil during operations. If possible, dispose of oil and •...
WARNING! During installation authorised personnel must wear individual safety devices. • Tmin=18°C • Tmax=30°C trAne will only consider itself responsible for the safety, • %rHmin=30% • %rHmax=70% reliability and performance of the machine if: Safety during maintenance work •...
INTRODUCTION Presentation of the system the JUPiter precision air conditioning units are designed for civil use and for all environments characterized by the presence of equipment with a high technological content: telephone and internet exchanges, data processing centres, meteorological rooms, laboratories and climate controlled warehouses. the Jupiter series consists of 2 types of conditioners: •...
Page 8
MODELS the code which distinguishes the models is composed of 4 characters: Identifying prefix of the Jupiter family Air discharge U = Upflow (upwards discharge) D = Downflow (downwards discharge) operating typology C = Chilled water units A = Air cooled direct expansion units W = Water cooled direct expansion units Fan typology V = Radial Electronically Commutated fans...
Page 9
SYMBOLS APPLIED TO THE MACHINES SYMBOL MEANING High voltage Organi in movimento Scariche elettriche Sharp edges RETTA –CONDENSAZIONE AD ARIA Bordi taglienti Organi in movimento Scariche elettriche SDAC/SUAC 0151B 0151A 0251B 0251A 0331A 0351A 0501A 0601A 1740 1740 1740 1740 1740 1740 1740...
(condensers). the room unit and external condenser form an autonomous sealed circuit once installed. the trAne remote condensers used with JUPiter units include a precise electronic system to regulate the fan speed to ensure trouble-free operation throughout the year under a wide range of external air temperatures.
Name and description of the principle components Model JUA*/JUW* Model JDA*/JDW* A User terminal B electrical panel door C Cover panel D electrical panel e Air Filter F Fans G Cooling circuit H Brazed plate heat exchanger (present in chilled water models)
Page 14
Description of the components A - User terminal Allows the unit to be turned on or off and the confi guration and visualization of the condition of the machine. • A1 LCD Display • A2 ALARM key:visualization and reset of alarms; when the alarm is activated, it fl ashes red •...
Check that the delivery is complete and inform the carrier of supplied on request from TRANE. However, the upflow units any damage to the unit which may be attributed too careless (upwards air flow) with air intake through the rear or front or inappropriate transportation.
Opening and removal of the front panel Installation of the mounting frame To install the unit on raised flooring using the mounting to open and remove the front panel proceed as follows: frame, carry out the following procedures: • a flexible seal at least 5 mm thick should be fitted between the raised floor panels and the mounting frame which should also be isolated from the metallic floor structure;...
Internal protection panels the fan compartment and electrical heaters are protected by a sheet metal covering for safety reasons and to allow the opening of the external panels without interfering with the safety devices on the unit. JD** JU** • pass the cables inside using the power supply cable inlet JD** JU**...
Connection to the drains PoWer SUPPLY CABLe (at customers at care) the condensed water drains from the tray through a siphoned flexible tube fitted in the unit. JD./JU.A-W (C-V) If the conditioner is fitted with a humidifier, the condensate 0115A - 0125A - 0133A - 0135A - 0150A - 0160 A drain tray and the humidifier drain connection must be connected to the drains of the building.
Refrigerant connections on air cooled units SUA*0151 SUA*0251 SUA*0331 SUA*0351 SUA*0501 SUA*0601 SDA*0151 SDA*0251 SDA*0331 SDA*0351 SDA*0501 SDA*0601 Installation guide 14 mm 16 mm 16 mm 18 mm 18 mm 22 mm WARNING! The pipes must always be protected from the sun. 12 mm 12 mm 12 mm...
Page 21
EN14276-1 e EN14276-2 lo spessore minimo Conforming to the S tandards EN14276-1 and EN14276-2 the minimum internal diameter of the valves supplied by trAne will not e tubazioni della linea di mandata del gas dove sono recommended thickness for the gas supply pipe where bends are made coincide with the diameter of the pipes.
qualificato. AVVERTENZA! L'acqua di raffreddamento deve contenere una percentuale di glicole etilenico Il circuito frigorifero è precaricato con azoto. (necessariamente di tipo passivato e quindi non Per eseguire la carica di refrigerante procedere nel seguente corrosivo) in funzione della minima temperatura Evacuation of the refrigeration circuit and charging of modo: Connection for water cooled units...
MANUAL START UP AND SHUT DOWN OF WA R N I N G ! D u r i n g p r o l o n g e d b r e a k s a THE UNIT spontaneous migration of the refrigerant may occur in the casing of the compressor, which may WARNING! Check that the refrigerant circuit has cause foaming of the oil and consequent damage...
SETTING AND ADJUSTMENT Selecting the power supply of the fans WARNING! Before establishing the electrical connection, make sure that the power supply is off. Also ensure that it is not possible to reconnect the power during the operation. WARNING! In the case of a unit with ducts, the load loss from the exhaust duct must be less than 100 Pa.
Page 25
Massima pressione disponibile in funzione della regolazione della velocità del ventilatore: Massima pressione disponibile in funzione della regolazione della velocità del ventilatore: Maximum available pressure depending on the fan speed regulation: ALGC000078 Allegato Generico Rev.0 J*AC J*WC 0115 - 0125 Tabelle J*AC J*WC 0115 - 0125 per manuali Amico...
Page 26
Massima pressione disponibile in funzione della regolazione della velocità del ventilatore: Maximum available pressure depending on the fan speed regulation: J*AV - J*WV 0115 - 0125 Air Flow Air Flow 1040 1300 1400 1500 1626 [m3/h] Fan Speed Discharge static pressure Fan Speed Discharge static pressure [Pa]...
Setting the regulation and safety devices Setting the air flow sensor After starting up the unit, set the following set points (see the FS differential pressure switch intervenes if the fan (or the microprocessor control manual): one of the fans) stops working. •...
Cleaning and replacing the filter MAINTENANCE To clean or change the filter proceed as follows: Checks every 3 months • rotate the closing blocks of the front panel by one Carry out the following checks every three months: quarter of a turn and remove the panel to access the •...
Page 29
Troubleshooting troubleshooting is made easier by the indications on the control panel display: when an alarm signal is displayed, consult the control panel instruction manual. if necessary, call the nearest Service Centre describing the nature of the fault and its possible cause displayed on the control. PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION...
Page 30
HUMIDITY CONTROL PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION A) the parameter settings on the control panel See control panel instruction manual. are not correct. rooM HUMiDitY too Check the latent load, fresh air conditions and B) the latent load is higher then expected. HiGH volume;...
Page 31
REFRIGERANT CIRCUIT PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION A) there is non-condensable air or gas in the refrigerant circuit, with bubbles in the flow sight evacuate the refrigerant circuit and recharge. glass; excessive sub-cooling. 1) Check the fan operation and rotation direction in the remote heat exchanger.
Page 32
PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION A) the room temperature is too low. See “rooM teMPerAtUre too LoW”. B) The air flow is too low or is absent. See “LoW Air FLoW”. C) the liquid line solenoid valve is not Check the valve opening. completely open.
Operating description CHILLED WATER UNITS (CW) the CW uses the availability of chilled water to control the room conditions. this version of JUPiter has a relatively simple construction and gives outstanding reliability. the microprocessor controls the modulating action of the 3 way (or optional 2 way) chilled water valve to give accurate control.
Name and description of the main components A User terminal Model JUC* Model JDC* B electrical panel door C Cover panels D electrical panel e Air Filter F Fans G Chilled water valve Description of the components A - User terminal Allows the unit to be turned on or off and the configuration and visualization of the condition of the machine.
Page 37
D - electric panel • D1 Magnetothermic - auxiliary - heater (optional) - humidifi er (optional) - fans • D2 Interface board • D3 Dirty fi lter sensor • D4 Air fl ow sensor • D5 Main switch • D6 Terminal board •...
Check that the delivery is complete and inform the carrier of supplied on request from TRANE. However, the upflow units any damage to the unit which may be attributed too careless (upwards air flow) with air intake through the rear or front or inappropriate transportation.
Page 39
Opening and removal of the front panel Installation of the mounting frame to open and remove the front panel proceed as follows: To install the unit on raised flooring using the mounting frame, carry out the following procedures: • a flexible seal at least 5 mm thick should be fitted between the raised floor panels and the mounting frame which should also be isolated from the metallic floor structure;...
Internal protection panels the fan compartment and electrical heaters are protected by a sheet metal covering for safety reasons and to allow the opening of the external panels without interfering with the safety devices on the unit. JD** JU** • pass the cables inside using the power supply cable inlet JD** JU**...
Filling the hydraulic circuit Connect the drainage tube of the unit to the collection tray (U4) of the humidifier. WARNING! The water used to fill the hydraulic Connect the drainage tube of the humidifier (U7) to the circuit must be filtered. drains of the building using a rubber or plastic tube, which is resistant to high temperatures (minimum 100 °C) with an WARNING! Filling the hydraulic circuit must only...
MANUAL START UP AND SHUT DOWN OF to turn the unit off, carry out the following procedure: THE UNIT • on the first screen of the user terminal, press the A5 or A7 buttons until the SWITCH OFF UNIT screen WARNING! Check that the refrigerant circuit has appears;...
Page 44
ALGC000078 Allegato Generico Rev.0 Tabelle Allegato per manuali Amico Generico C08003 Tabelle per manuali Amico Pag. 7 / 11 CENTRIFUGAL FANS Nominal fan regulation (to have the nominal airflow with ESP=20Pa) Regolazione nominale del ventilatore (per avere la portata aria nominale con ESP=20Pa) Regolazione nominale del ventilatore (per avere la portata aria nominale con ESP=20Pa) UNIT WITHOUT ELECTRICAL RESISTANCES UNIT WITH ELECTRICAL RESISTANCES...
Page 45
J*CC0030* Air Flow Air Flow 1150 1500 2000 2300 2339 [m3/h] Fan Speed Discharge static pressure Discharge static pressure Fan Speed [Pa] [Pa] [Pa] [Pa] [Pa] J*CC0040* Air Flow Air Flow 1940 2500 3000 3360 3470 [m3/h] Fan Speed Discharge static pressure Fan Speed Discharge static pressure [Pa]...
0060 Massima pressione disponibile in funzione della regolazione della velocità del ventilatore: Massima pressione disponibile in funzione della regolazione della velocità del ventilatore: Maximum available pressure depending on the fan speed regulation: J*CCV0020* J*CCV0020* Air Flow 1040 1370 1520 1610 1956 [m3/h] Air Flow...
Setting the air flow sensor MAINTENANCE the FS differential pressure switch intervenes if the fan (or Checks every 3 months one of the fans) stops working. Carry out the following checks every three months: the factory set point of the FS differential pressure switch •...
Cleaning and replacing the filters Servomotor and chilled water valve To clean and replace the filters carry out the following if necessary (in the event of a fault in the servomotor or the procedures: control system) manually move the valve: •...
Troubleshooting troubleshooting is made easier by the indications on the control panel display: when an alarm signal is displayed, consult the control panel instruction manual. if necessary, call the nearest Service Centre describing the nature of the fault and its possible cause displayed on the control. PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION...
Page 50
HUMIDITY CONTROL PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION A) the parameter settings on the control panel See control panel instruction manual. are not correct. Check the latent load, fresh air conditions and B) the latent load is higher then expected. volume; external air infiltration. rooM HUMiDitY too See: Control system user instruction manual;...
ACCESSORIES Humidifier CONDIZIONATORI D'ARIA DI PRECISIONE UMIDIFICATORE a di un umidificatore a elettrodi immersi (versioni D e H). Il gruppo di produzione del 1. Scheda di interfaccia umidificatore: SIU; ( interna al quandro elettrico ) . 2. Trasformatore amperometrico per la misura dell’intensità...
Operating principle In the electrode boiler humidifier, the current flowing between the electrodes in the water in the cylinder generates the heat necessary to boil the water. By controlling the water level and the concentration of salt measured in the steam cylinder (U1) using the feed water solenoid valve (U8) and the boiler cylinder electric drainage valve (U9), the electric current is regulated by means of an amperometric transformer (U11).
Maintenance the only maintenance required is periodic inspection and cleaning of the steam boiler components. this should be carried out at least every six months, preferably before the summer holiday shutdown. BOILER CYLINDER Limescale deposits must be cleaned periodically from the electrodes and particles of limescale must be removed from the filter at the base of the cylinder.
Electric heaters Jupiter units can be equipped with electric heaters. For each model there are two levels available: standard and improved. The fi nned elements are characterised by maintaining low power density of the surfaces in a highly effi cient way, therefore limiting overheating of the elements and consequently increasing their lifespan.
Replacing the electrical heaters WARNING! Before replacing the electrical heaters, disconnect the power supply from the unit. Make sure that it is not possible for the power to be turned on again while they are being replaced. WARNING! The heaters must only be replaced by a qualified electrician. the total capacity of the electrical heaters is subdivided into more elements, each with a capacity equal to 2 or 3 kW based on the size of the unit.
Connection to fresh air intake The unit can be made ready for the intake of fresh air through an optional filter. The optional module for the fresh air intake, containing the filter cartridge, must be applied on the left side of the unit during the installation phase and correspond to the holes which introduce the air into the fan compartment.
Discharge temperature threshold sensor (only on CHILLED WATER models) An ntC temperature sensor is an optional accessory which maintains the supply air temperature of the unit above a threshold value. the sensor is connected to the microprocessor control system as described in the electrical diagram of the unit.
Page 58