Chapter 2 LT140 Installation
2.3 Installation Area
2.3.2

Notes of Mounting in the Rack

The rack must be a 19 inch rack and meet the EIA standard universal pitch.
The dimension of the prop for fixing the rack must meet
The dimensions of the protruding objects such as props in the rack must meet
The hole geometries of the props must be 9mm corner holes or 6.8mm round holes.
There must be a vent hole in the anteroposterior position and the library must be coolable enough.
(The temperature in the rack not to exceed the limited temperature. Refer to "Operating" under "Tempera-
ture" in
Table 2.1
Take measures to ensure the physical stability of the entire rack (including the pulled out status of
modules from a rack). If the rack is equipped with the anti-toppling feature, be sure to use it. In addition,
mount the LT140 to the lowest position available. The ideal installation height is under 24U (1.2m). If the
LT140 is mounted with other devices, the heavier devices must be mounted at the very bottom and the
ideal total installation height is under 31U (1.5m).

Figure 2.2 Explanation drawing of the dimensions (top view)

Props of the rack
Front
Front door
FUJITSU Storage ETERNUS LT140 Tape Library User's Guide -Site Planning-
for details.)
Inside dimension 694 – 890mm
No obstructions between the props
(shaded area)
15mm or longer
15mm or longer
43mm
23
Copyright 2018 FUJITSU LIMITED
Figure 2.2
and
Figure
ETERNUS LT140
892mm
Top view
2.3.
Figure 2.2
and
Figure
2.3.
Rack rails
Props of the rack
Rear door
Space for cables
60mm or larger
P3AG-3712-01ENZ0